1. Before installation, read the user manual carefully to get familiar with product information
and safety precautions.
2. Use insulated tools when installing the equipment.
3. Only engineers certified by Huawei or its agent are allowed to install, commission, and
maintain the UPS. Otherwise, personal injury or equipment damage may occur, and the
resulting UPS faults are beyond the warranty scope of Huawei.
4. This document describes the installation procedure for a single UPS. For details about how to
install a parallel system, contact Huawei technical support.
2
Installing the
UPS
2.1
Determining the UPS Installation Position
The UPS can be installed on channel steel or the floor. Install the UPS based on site requirements.
Floor installation: Determine the UPS mounting holes using the marking-off template, drill
holes, and install the expansion sleeves of the M12x60 expansion bolts in the mounting holes.
Channel steel installation: Ensure that the distance between the outer surfaces of two pieces
of channel steel is 800 mm and secure the channel steel to the floor using expansion bolts.
Huawei does not provide channel steel or expansion bolts used for securing channel steel. The
customer should purchase channel steel (recommended width: 50 mm or more) and
expansion bolts.