Controls Interface

Settings Screen

The Settings screen provides a user the ability to adjust settings justified to support
daily tasks. The layout provides a list of sub-menus, organized by typical subsystem.
This organization allows each subscreen to be shorter in length which should improve
the users navigation.
Table 21
Settings Screen
Description
Chiller
Front Panel Chilled Water Setpt
Front Panel Demand Limit
Front Panel Ice Build Cmd
Front Panel Ice Termn Setpt
Design Delta Temp
Setpoint Source
Leaving Water Temp Cutout
Feature Settings
Low Ambient Lockout Setpoint (CCAF)
Low Ambient Lockout (CCAF)
Chilled Water Reset
Return Reset Ratio
Return Start Reset
Return Maximum Reset
Outdoor Reset Ratio
Outdoor Start Reset
Outdoor Maximum Reset
Ext Chilled Water Setpoint
Ice Building
Hot Gas Bypass
Operational Pumpdown
ICS Address
Units
Resolution, Default
Temperature
+ or - XXX.X
X
Text
On/Auto
Temperature
XXX.X
Temperature
XXX.X
Text
(BAS/Ext/FP , Ext/ Front Panel,
Front Panel), BAS/Ext/FP
Temperature
XX.X
Temperature
XXX.X
Text
(Enable, Disable), Enable
Text
(Constant, Outdoor, Return,
Disable), Disable
Percent
XXX
Temperature
XXX.X
Temperature
XXX.X
Percent
XXX
Temperature
XXX.X
Temperature
XXX.X
Text
(Enable, Disable), Disable
Text
(Enable, Disable), Disable
Text
(Enable, Disable), Disable
Text
(Enable, Disable), Disable
Text
XX
67