UCP2 Board Dip Switch Settings
Several of the UCP2 modules have dip switch settings on them, used to set up the board for 2-10
VDC or 4-20 mA signal inputs and/or outputs of the boards. The following are the various switch
settings.
Chiller Module
External Base Loading
Options Module
External Current Limit
External Chilled Water
Tracer COM 3
Tracer COM 4
IPC Buffer
CVHE-SB-32A
Module Dip Switch Settings
Switch
0-10V
SW2-1
OFF
Switch
0-10V
SW2-1
OFF
SW3-1
OFF
Switch
-1
SW1
OFF
Switch
-1
SW1
OFF
Switch
-1
SW1
OFF
ON (SW2-2 and SW2-3 are not used)
4-20mA
ON (SW2-2 and SW2-3 are not used)
ON (SW3-2 and SW3-3 are not used)
-2
-3
OFF
OFF
-2
-3
ON
OFF
-2
-3
OFF
ON
4-20mA
47