Table 11
Electrical Data CCAF and CGWF High Condensing Temperature (90-130 F) Units
Unit Size
Unit Wiring Data
Rated
Voltage
20
208/230
380
460
575
400/50
25
208/230
380
460
575
400/50
30
208/230
380
460
575
400/50
40
208/230
380
460
575
400/50
50
208/230
380
460
575
400/50
60
208/230
380
460
575
400/50
Notes:
1. Minimum Circuit Ampacity is 125% of the largest compressor RLA plus 100% of the remaining compressor(s) RLA, per NEC 440-32 and NEC 440-33.
2. Maximum Fuse Size is 225% of the largest compressor RLA plus 100% of the remaining compressor(s) RLS, per NEC 440-30.
3. Recommended Dual-Element Fuse Size is 175% of the largest compressor RLA plus 100% of the remaining compressor(s) RLA, Per NEC 430-152.
4. Use copper conductors only.
5.Compressor motor Voltage utilization range is:
Rated Voltage--- Utilization Range
208/230 ---188-253
380 ---342-418
460 ---414-506
575 ---517-633
400/50 - 360-440
46
Installation Electrical
Minimum
Max Fuse
Circuit
Size
Ampacity
88
125
45
60
38
50
32
45
38
50
112
150
59
80
50
70
40
60
48
70
131
175
70
100
59
80
47
60
56
80
166
200
85
100
72
80
60
70
72
80
209
250
110
125
93
110
75
90
90
110
247
300
132
150
111
125
89
100
106
125
Compressor Motor Data
Recommended
Qty - Size
Duel Element
Fuse Size
110
2 -10
60
50
40
50
150
1 -15
1 - 10
80
70
60
70
175
2 - 15
90
80
60
80
200
4 - 10
100
90
70
90
250
2 - 15
2 - 10
150
110
90
110
300
4 - 15
150
125
110
125
RLA
LRA
39
251
20
142
17
117
14
94
17
117
58/39
376/251
31/20
215/142
26/17
178/117
21/14
143/94
25/17
178/117
58
376
31
215
26
178
21
143
25
178
39
251
20
142
17
117
14
94
17
117
58/39
376/251
31/20
215/142
26/17
178/117
21/14
143/94
25/17
178/117
58
376
31
215
26
178
21
143
25
178
CGWF-SVX01A-EN