Event States; Controller Settings; Unit Ip Address - Carrier AquaEdge 19DV Operation And Troubleshooting

Two-stage high-efficiency semi-hermetic centrifugal liquid chillers with pic6 controls
Table of Contents

Advertisement

Event States

An event state is a specific set of conditions that the controller
may encounter when controlling the chiller. Event states are re-
peatable and predictable, and represent known states of the
control. When the control is in a particular state, a unique mes-
sage is associated with that state. The event state messages are
displayed on the default screen of the control panel and are list-
ed in Table 18.
Table 18 — Event States
EVENT NO.
1
Chiller Off
2
Chiller Tripout
3
Pumpdown/Lockout
4
Terminate Pumpdown/Lockout
5
Guide Vane Calibration
6
Quick Test in Progress
7
Ice Build Done
8
Ice Build in Progress
9
Free Cooling in Progress
10
Auto Restart Pend
11
Condenser Flush in Progress
13
Envelope Control Valve Calibration
14
Damper Valve Calibration
15
The 1st time 30-Min Ref Lubricating
20
Startup Inhibited - Loadshed in Effect
21
Prestart Check in Progress
22
Timeout - Delay to Start in
23
Recycle in Progress
24
Startup in Progress
25
Swift Restart In Progress
30
Ramp Loading - Temperature
31
Ramp Loading - Motor Load
32
Ramp Loading - Capacity Inhibit
35
Demand Limit - by Local Signal
36
Demand Limit - by 4-20 mA
37
Demand Limit - by Network Command
38
Demand Limit - by Loadshed Redline
39
Demand Limit - Capacity Inhibit
40
Demand Limit - Capacity Decrease
41
Demand Limit - Inhibit Clamp
45
Override - High Condenser Pressure
47
Override - High Motor Temperature
48
Override - Low Evap Refrig Temp
49
Override - High Compressor Lift
50
Override - High Bearing Temp
51
Override - Low Discharge Superheat
52
Override - Manual VFD Speed Target
53
Override - High Motor Current
54
Override - High Discharge Temp
55
Override - Low Source Temp
60
Running - Temp Reset by 4-20mA Signal
61
Running - Temp Reset by Remote Temp Sensor
62
Running - Temp Reset by Water DT
63
Running - Cooling Leaving Chilled Water
64
Running - Cooling Entering Chilled Water
65
Running - Heating Leaving Cond Water
66
Running - Heating Entering Cond Water
67
Envelope Control - Surge Correction
68
Envelope Control - Acts Before Recycle Shutdown
69
Envelope Control - Low Load Application
70
Envelope Control - Forced
71
Running - VFD Rampdown
72
Running - Guide Vane 1 Position Forced
73
Running - VFD Speed Forced
74
Optimal Operation
75
Surge Prevention
76
Surge Protection
77
Running - VFD Overcurrent
78
Envelope Control - Delta Tx
DESCRIPTION
Table 18 — Event States (cont)
EVENT NO.
79
Running - Damper Valve Forced
80
Operation - Oil EXV Forced
81
Running - Head Pressure Valve Forced
82
Purge - Forced
83
Running - Guide Vane 2 Position Forced
84
Operation - Refrigerant Lub Forced
85
Running - Vapor Source Valve Forced
90
Shutdown - Normal
91
Shutdown - Alarm
93
Shutdown - Recycle
94
Shutdown - Recycle Ice Build
95
Shutdown - Compressor Deenergized
96
Shutdown - Emergency Stop
97
Transducer Calibration in Effect
98
ISM Calibration in Effect

CONTROLLER SETTINGS

The controller settings are accessible through the Configuration
Menu when logged into the Factory account.

Unit IP Address

On the Configuration Menu screen, press Ethernet Configura-
tion to display the network parameters. See Fig. 46.
NOTE: You must request an IP address, the subnet mask, and the
default gateway from the system administrator before connecting
the unit to the local Ethernet network.
To change IP address manually, select Ethernet Configuration
from the System Configuration Menu. See Fig. 46.
Fig. 46 — Ethernet Configuration
Enter the new address and validate it by pressing Apply. Return
to the Network screen and enter the subnet mask and default
gateway using the same method. Then return to the application
and save the changes. See Fig. 47.
42
DESCRIPTION

Advertisement

Table of Contents
loading

Table of Contents