Installation Environment Requirements - Helios CUBE User Manual

Lithium-ion battery storage
Table of Contents

Advertisement

HELIOS CUBE BS4850-SH
User Manual
Tool
ESD gloves
Insulated gloves
Hydraulic pliers
Cable tie
3.3 I
NSTALLATION
Despite careful design and construction, electrical devices can cause fires.
Do not install the product in areas containing highly flammable materials or gases.
Do not install the product in potentially explosive atmospheres.
The product is protected to IP65 and can be installed indoors or outdoors.
Do not install the product in a place where a person can be easy to come into contact with its
enclosure.
Do not install the product at a place within children's reach.
The product will be corroded in salt areas, and the salt corrosion may cause fire. Do not install the
product outdoors in salt areas. A salt area refers to the region within 500 meters from the coast or
prone to sea breeze. The regions prone to sea breeze vary depending on weather conditions (such as
typhoons and monsoons) or terrains (such as dams and hills).
Keep the installation place as dry as possible with good ventilation for heat dissipation.
When installed under direct sunlight, performance de-rate may be initiated due to additional
temperature rise.
Helios New Energy Technology (Australia) Pty Ltd
Appearance
E
R
NVIRONMENT
EQUIREMENTS
Description
Used to prevent the electrostatic discharge
(ESD) from damaging a board or other
electrostatic sensitive devices (ESSDs) when
you insert or remove a board or hold an
ESSD.
Used to insulate hands.
Used to crimp the OT terminals and JG
terminals with a large cross-sectional area of
2
2
10 mm
, 16 mm
, 25 mm
Used to bind cables.
3. Installation
2
2
, or 35 mm
.
15

Advertisement