Instruction Manual
D104263X012
March 2018
Model DFA 7236
Detonation Flame Arrestor

Table of Contents

Introduction ............................................................................1
Principle of Operation ............................................................2
Specifications ........................................................................2
Installation .............................................................................4
Detonation Flame Arrestor.....................................................4
Maintenance ..........................................................................6
Reassembly Instructions .......................................................6
!
Failure to follow these instructions or to
properly install and maintain this equipment
could result in an explosion, fire and/or
chemical contamination causing property
damage and personal injury or death.
Enardo detonation flame arrestor
must be installed, operated and
maintained in accordance with federal,
state and local codes, rules and
regulations and Emerson Process
LLC (Emerson) instructions.
Failure to correct trouble could result in a
hazardous condition. Call a qualified service
person to service the unit. Installation,
operation and maintenance procedures
performed by unqualified person may
result in improper adjustment and unsafe
operation. Either condition may result in
equipment damage or personal injury. Only
a qualified person shall install or service the
detonation flame arrestor.

Introduction

Scope of the Manual
This Instruction Manual provides instructions for
installation, startup and maintenance information for the
Model DFA-7236 detonation flame arrestor.
Model DFA 7236
Figure 1. Typical Model DFA-7236
Detonation Flame Arrestor
Product Description
The DFA Series detonation flame arrestor represents the
best value in flame arrestor protection. The detonation flame
arrestor provides protection against flame propagation in piping
systems that are manifolded or have long run-up distances.
These are typically used for extended pipe length or multiple
pipe bend configurations to stop high pressures and flame
velocities with detonations and overdriven detonations. It
also stops confined and unconfined, low and high-pressure
deflagration. The design is unique in the ability to provide large
flame channels which requires less frequent maintenance and
greater ease in cleaning when service is required, translating
to less down time. DFA Series detonation flame arrestors are
bi-directional and proven to stop an ignited flammable vapor
mixture approaching from either direction that can be travelling
at subsonic or supersonic velocities. The element assembly
offers maximum flow to pressure drop characteristics enhancing
the value of the flame arrestor in any system.
The DFA Series is designed with flanged connections. The
arrestor provides the option of the removal of the flame cell
element assembly for cleaning and replacement with the
arrestor removed from the ping.

Advertisement

Table of Contents
loading

Summary of Contents for Emerson Enardo DFA 7236

  • Page 1: Table Of Contents

    The DFA Series detonation flame arrestor represents the regulations and Emerson Process best value in flame arrestor protection. The detonation flame Management Regulator Technologies Tulsa, arrestor provides protection against flame propagation in piping LLC (Emerson) instructions.
  • Page 2: Principle Of Operation

    Model DFA 7236 Specifications The Specifications table lists the specifications for the detonation flame arrestor. The following information is stamped on the nameplate attached to the arrestor: model number, flange size and rating, maximum initial operating pressure, gas group, date of manufacture and serial number;...
  • Page 3 Model DFA 7236 Figure 2. Cut-away view of DFA Series Detonation Flame Arrestor Detonation Housing Connection Housing Element Connection Options Flame Size Size Material Material Type Arrestor Group DFA = 72 = 72 in. 36 = 36 in. IIA (D) C = Carbon steel 4 = 304 SST F = Flat face...
  • Page 4: Installation

    Model DFA 7236 Bends in piping, pipe expansions and/or contractions, The arrestor should be positioned such that the entire valves orifice plates or flow obstructing devices of any kind arrestor is accessible for removal. Install the unit such that cause turbulent flow. Turbulent flow enhances mixing of the the flow arrow located on the unit points in the direction combustible gases, greatly increasing the combustion intensity.
  • Page 5 Model DFA 7236 CENTER OF GRAVITY CENTER OF GRAVITY Figure 4. Lifting Diagram...
  • Page 6: Maintenance

    Do not clean the arrestor elements by rodding Under no circumstance shall any element with wire or other hard objects to remove blockages. assembly not provided by Emerson be used Cleaning the elements with wire or other hard objects in this assembly. Failure to use the correct...
  • Page 7 Model DFA 7236 Table 1. Tightening Steps and Torque Values TIGHTENING STEPS AND TORQUE (FT-LBS / N•m) MODEL BOLT SIZE DFA-7236 1.50 in. Snug 80 / 110 250 / 340 450 / 610 700 / 950 1000 / 1360 1. Using machine oil as lubricant. See Bolt Lubrication section on page 7 and torque correction factors for other lubricants in Table 2. Table 2.
  • Page 8: Management Regulator Technologies Tulsa

    Technologies, Inc. All rights reserved. 03/18. Emerson Automation Solutions The Emerson logo is a trademark and service mark of Emerson Electric Co. All other marks are the property of their prospective owners. Enardo™ is a mark owned by Regulator Technologies Tulsa, LLC, a...