netvox R718NL3 User Manual page 8

Wireless light sensor and 3-phase current meter
Hide thumbs Also See for R718NL3:
Table of Contents

Advertisement

byte (99): Device Type 0x99 - R718NL3 Series
nd
2
rd
3
byte (02): Report Type
th
4
byte (24): Battery-3.6v , 24Hex=36 Dec
th
5
byte (01): Multiplier2-1
th
6
byte (01): Multiplier3-1
byte (00000003): Illuminance -3Lux
th
th
7
-10
th
11
byte (00): Reserved
Note:
1.When the current which is detected by the R718NL3 series exceeds 65535mA, the Multiplier column will be displayed as
"10".(Because the current value of the payload is 2 bytes, it can be displayed up to 0xFFFF.)
2. The real current should convert with Current* Multiplier
5.2 Example of ConfigureCmd
FPort:0x07
Bytes
1
CmdID
CmdID– 1 byte
DeviceType– 1 byte – Device Type of Device
NetvoxPayLoadData– var bytes (Max=9bytes)
Description
Device
ConfigReport
Req
ConfigReport
Rsp
R718NL3
ReadConfig
series
ReportReq
ReadConfig
ReportRsp
(1) Configure report parameters MinTime = 1min, MaxTime = 1min, CurrentChange = 100mA, IlluminanceChange = 100Lux
Downlink: 0199003C003C0064006400
The device returns:8199000000000000000000 (Configuration succeeded)
1
DeviceType
Cmd
Device
ID
Type
MinTime
0x01
(2bytes)
Unit:s
0x81
0x99
0x02
MinTime
0x82
(2bytes)
Unit:s
36*0.1v=3.6v
Var (Fix =9 Bytes)
NetvoxPayLoadData
NetvoxPayLoadData
MaxTime
CurrentChange
(2bytes)
(2byte)
Unit:s
Unit:1mA)
Status
(0x00_success)
(9Bytes,Fixed 0x00)
MaxTime
CurrentChange
(2bytes)
(2byte)
Unit:s
Unit:1mA)
7
Illuminance
change
(2bytes Unit:1Lux)
Reserved
(8Bytes,Fixed 0x00)
Reserved
Illuminance
change
(2bytes Unit:1Lux)
Reserved
(1Byte)
Fixed 0x00)
Reserved
(1Byte)
Fixed 0x00)