COMPONENT IDENTIFICATION

(A)
(B)
(C)
(D)
1
2
3
X10
X1
PWR
ERR
RD
RUN
SD
STATION ADD.
B.RATE
4
5
6
7
1
2
3
(F)
(A) Status Indicator LED *
1
(B) Station Address Setting Rotary SW
(C) Baud Rate Setting Rotary SW
(D) Operating Mode Setting DIP SW (SW1)
(E) PC Configurator Jack
(F) CC-Link, Power Supply Terminals
(G) Output Terminals
*1. Refer to 'Status Indicator LED' section for detailed information.
■ STATUS INDICATOR LED
ID
COLOR FUNCTION
PWR
Red
Turns on when the internal 5V is sup-
plied normally.
RUN
Red
Turns on when the refresh data is re-
ceived normally.
ERR
Red
Turns on when the received data is
abnormal.
SD
Red
Turns on when the module is transmit-
ting.
RD
Red
Turns on when the module is receiving.
■ STATION ADDRESS
Station Address is selected between 1 and 64 in decimal.
The left switch determines the tenth place digit, while the
right switch does the ones place digit of the address.
Station Address Setting (x1)
Station Address Setting (x10)
■ BAUD RATE
Baud Rate is selected with the rotary switch.
0 : 156 kbps
1 : 625 kbps
2 : 2.5 Mbps
3 : 5 Mbps
4 : 10 Mbps
Baud Rate Setting
SEN TRONIC
(E)
4
5
6
7
8
CNFG.
9
10
6
7
8
1
2
3
4
5
(G)
056 222 38 18
AG
■ OPERATING MODE
(*) Factory setting
• Extension (SW1-1, 1-2)
SW1-1 SW1-2 EXTENSION
OFF
OFF
No extension (*)
ON
OFF
Discrete input, 8 or 16 points
OFF
ON
Discrete output, 8 or 16 points
• Output at the loss of communication (SW1-4)
SW1-4 OUTPUT AT THE LOSS OF COMMUNICATION
OFF
Reset the output (to -15%)
ON
Hold the output (*)(maintains the last data received
normally)
Note: Be sure to set unused SW1-3 and 1-5 through 1-8 to
OFF.
■ POWER SUPPLY, CC-LINK TERMINAL ASSIGNMENT
4
DA
1
DB
NO.
ID
1
DB
2
SLD
3
FG
4
DA
5
DG
6
+24V
7
0V
■ OUTPUT TERMINAL ASSIGNMENT
6
7
NC
I0
1
2
NC
COM0
NO.
ID
FUNCTION
1
NC
No connection
2
COM0 Common 0
3
NC
No connection
4
COM1 Common 1
5
NC
No connection
■ EXTENSION MODULE
Combinations with all extension modules are selectable.
mailbox@sentronic.com
www.sentronic.com
R7C-YS2
5
6
7
DG
+24V
0V
2
3
SLD
FG
FUNCTION, NOTES
White
Shield
FG
Blue
Yellow
Power input (24V DC)
Power input (0V)
8
9
10
NC
I1
NC
3
4
5
NC
COM1
NC
NO.
ID
FUNCTION
6
NC
No connection
7
I0
Current 0
8
NC
No connection
9
I1
Current 1
10
NC
No connection