5 PROGRAMMING

5.2 When Remote Net Ver. 1 Mode Is Used

5.2.1 Conditions of Program Example

PLC CPU
Device X
X400 to X40F
5
X410 to X41F
Device Y
Y400 to Y40F
Y410 to Y41F
Device D
Device D
In the program example (refer to Section 5.2.4) that uses the RRPA instruction (automatic refresh
parameter setting) with the ACPU/QCPU (A mode), RWr0 to RWr8 are assigned to D456 to D464.
5 - 2
The program examples in this section are created under the following conditions.
(1) System configuration
PLC CPU
Master station
(X0 to X1F/Y0 to Y1F)
I/O (Input 64 points)
(X20 to X5F)
I/O (Output 64 points)
(Y60 to Y9F)
(2) Relationships between PLC CPU, master module and
AJ65VBTCU-68DAVN
Address
E0
H
E1
H
160
H
161
H
1E0
D200
H
1E1
D201
H
1E2
D202
H
1E3
D203
H
1E4
D204
H
1E5
D205
H
1E6
D206
H
1E7
D207
H
1E8
D208
H
1E9
D209
H
1EA
D210
1EB
D211
2E0
D300
H
2E1
D301
H
2E2
D302
H
2E3
D303
H
2E4
D304
H
2E5
D305
H
2E6
D306
H
2E7
D307
H
2E8
D308
H
D309
2E9
H
D310
2EA
H
D311
2EB
H
AJ65VBTCU-68DAVN
(Station number 1)
Master module
Remote input (RX)
RX00 to RX0F
RX10 to RX1F
Remote output (RY)
RY00 to RY0F
RY10 to RY1F
Remote register (RWw)
RWw0
RWw1
RWw2
RWw3
RWw4
RWw5
RWw6
RWw7
RWw8
RWw9
RWwA
H
RWwB
H
Remote register (RWr)
RWr0
RWr1
RWr2
RWr3
RWr4
RWr5
RWr6
RWr7
RWr8
RWr9
RWrA
RWrB
MELSEC-A
AJ65VBTCU-68DAVN
(Station number 1)
Remote input (RX)
RX00 to RX0F
RX10 to RX1F
Remote output (RY)
RY00 to RY0F
RY10 to RY1F
Remote register (RWw)
RWw0 CH.1 digital value setting
RWw1 CH.2 digital value setting
RWw2 CH.3 digital value setting
RWw3 CH.4 digital value setting
RWw4 CH.5 digital value setting
RWw5 CH.6 digital value setting
RWw6 CH.7 digital value setting
RWw7 CH.8 digital value setting
RWw8 Analog output
enable/disable setting
RWw9 CH.1 to CH.4 output range
setting
RWwA CH.5 to CH.8 output range
setting
RWwB HOLD/CLEAR setting
Remote register(RWr)
RWr0 CH.1 check code
RWr1 CH.2 check code
RWr2 CH.3 check code
RWr3 CH.4 check code
RWr4 CH.5 check code
RWr5 CH.6 check code
RWr6 CH.7 check code
RWr7 CH.8 check code
RWr8 Error code
RWr9 Reserved
RWrA Reserved
RWrB Reserved
5 - 2