Installation Of Cables / Pin Connection; Easyteach Chart / Switching Function Of The Outputs - Rechner Sensors EasyTeach Instruction Manual

Capacitive leak sensors self-adjusting (mag)
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 6
Installation of cables
Wiring of the sensor should be routed separately or screened from heavy conductor lines, as in extreme
cases inductive peak voltages can destroy the sensors despite the integrated protective circuit. Screened
cable or twisted lines are recommended, especially for longer cable runs > 5 m.
Units with strong fields nearby, e. g. high power walkie-talkies, or noise sources in the lower frequency
range, e. g. long, middle or short wave transmitters should not be operated close to the sensors or additional
measures have to be taken in order to eliminate incorrect operation.
Pin connection
4
3
1
2
EasyTeach chart
EasyTeach chart
Output A1 = normally open /
Output A2 = normally closed
Switching function of the outputs
Free hold
Place on container bottom
Ready for use
Leakage detection
Change of position
8
Pin connection for pluggable sensors (top view)
The EasyTeach chart is used for optical menu navigation. They
illustrate the flashing behaviour of the LED.
Sensor free, ready for automatic adjustment
Sensor is in the adjustment phase (placing the sensor on the bottom of the container)
Working area, sensor active
Sensor detects leakage
Sensor has a slight deviation of its position, e.g. sensor is tilted
LED
flashing / 1 Hz
flashing / 5 Hz
flashing / 2 Hz
Output A1
Output A2
low
high
low
high
high
high
high
low
low
high

Advertisement