Huawei UPS5000-E-400K-FMS Quick Manual page 11

Hide thumbs Also See for UPS5000-E-400K-FMS:
Table of Contents

Advertisement

2. Set the language, time, date, network parameters, system parameters, and battery
parameters on the Settings Wizard screen.
3. After you perform the settings, the Bypass mode and No battery alarms are reported by the
MDU and do not need to be cleared. If there is any other alarm, you need to rectify the fault.
4. If the system has connected to the remote EPO switch, you need to choose Monitoring >
UPS System > Running Parameter > System Settings on the WebUI and set EPO detection
to Enable.
5. View the system running status diagram on the MDU to check that the UPS is working in
bypass mode.
5.3
Starting the Inverter
1. On the main menu, choose Common Functions and
tap Inv. ON.
2. In the displayed login window, enter the user name and
password, and tap
3. In the displayed dialog box, tap Yes to start the inverter.
System User
admin (system
administrator)
operator (common user)
.
LCD Preset Password
000001
000001
11
To ensure system security,
change the LCD and WebUI
passwords after the first login.
WebUI Preset Password
Changeme
Changeme