5.1

Powering On the UPS

(For a UPS in full configuration) Turn on the UPS bypass input switch, output switch, and mains
After the UPS is powered on, initialization begins. The MDU displays an initialization progress bar.
5.2

Starting the Inverter

If the UPS is powered on for the first time, you need to obtain the startup password from the
Service Expert app. Skip this step if the UPS is not powered on for the first time.
The Service Expert app can be downloaded from HUAWEI AppGallery and can only run on
Android.
The Settings Wizard screen may vary with versions. The parameters depend on the actual
product.
1. Obtain the startup password.
Download and install the Service Expert app.
On the app home screen, tap StartUp to access the Set Startup screen.
Insert the WiFi module into the USB port on
the MDU. Enable the mobile phone WLAN,
search for the UPS_WIFI signal, and connect to
the WiFi signal. The password is Changeme.
Set the Site and Device Type as required, and
connect the device. Set IP to 192.168.0.10, Port
to 443, Username to admin, Password to
Changeme, and tap Login.
After login, tap Power-on password
activation on the screen. A message is
displayed, indicating whether to start the UPS.
Tap OK.
Turn on the upstream bypass and mains input switches.
Use the app to
start the UPS
online?
Yes
input switch.
No, start
the UPS
offline
Set Site and Device Type as required,
and tap Offline Activation.
Enter Bar code and Verification code
obtained from the LCD on the Offline
Activation screen. Tap Generate PWD to
generate a startup password.
Enter the generated password in the
password textbox on the LCD to start the
UPS.