Fujitsu AUYG18LVLB Design & Technical Manual page 211

Simultaneous multi
Hide thumbs Also See for AUYG18LVLB:
Table of Contents

Advertisement

¢ Installation procedure for Twin type and Double twin type
CAUTION
• Do not mistake the direction of connection.
• Set the piping from the branch pipe to the indoor units to be the same length. (Max. difference: 8
m)
• Shorten the length of the piping after branching as much as possible. (Max. length: 20 m)
1.
Check the direction of connection.
2.
If the diameter of the connection piping is too large, use a pipe cutter to cut as shown below.
3.
Check the positioning of branch pipes.
If it is placed horizontally, keep it within ±15°. Otherwise, it will not separate the refrigerant
evenly, causing a reduction in performance.
3-4. Branch pipes
Outdoor unit
Cut in the center of the connections
locally purchased
Indoor unit
Indoor unit
• Always use a pipe cutter.
• After cutting, remove the burr and clean the cut section.
+15°
-15°
o t
n i
d
o
r o
u
n
t i
- 203 -