Switching Cycles - Siemens SIMATIC ET 200SP Equipment Manual

Digital output module rq 4x120vdc-230vac/5a no ma st
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

6.2

Switching cycles

Switching capacity and lifetime of the contacts
With an external protective circuit, the contacts will last longer than specified in the table.
This table shows the switching capacity and lifetime of the relay contacts:
Table 6- 1
For resistive load
For inductive load in
accordance with
IEC 947-5-1 DC 13/
AC15
For inductive load in
accordance with
IEC 947-5-1 DC 13/
AC15
Digital output module RQ 4x120VDC-230VAC/5A NO MA ST (6ES7132-6MD00-0BB1)
Equipment Manual, , A5E36107692-AB
Switching capacity and lifetime of the relay contacts
Resistive load
24 V DC
60 VDC
120 VDC
48 VAC
60 VAC
120 VAC
230 VAC
24 V DC
60 VDC
120 VDC
48 VAC
60 VAC
120 VAC
230 VAC
Voltage
5.0 A
4.0 A
2.0 A
1.0 A
0.5 A
0.1 A
0.5 A
0.2 A
2.0 A
2.0 A
5.0 A
3.0 A
2.0 A
1.0 A
0.5 A
5.0 A
3.0 A
2.0 A
1.0 A
0.5 A
2.0 A
1.0 A
0.5 A
0.5 A
0.2 A
1.0 A
1.0 A
2.0 A
1.0 A
0.5 A
0.1 A
2.0 A
1.0 A
0.5 A
Technical specifications
6.2 Switching cycles
Current
Switching cycles (typi-
0.1 million
0.2 million
0.5 million
1.6 million
4 million
7 million
1.6 million
1.6 million
1.6 million
1.2 million
0.1 million
0.2 million
0.4 million
0.8 million
1.5 million
0.1 million
0.2 million
0.4 million
0.8 million
1.5 million
0.1 million
0.2 million
0.5 million
0.2 million
0.5 million
0.7 million
0.5 million
0.1 million
0.3 million
1 million
2 million
0.1 million
0.3 million
1 million
cal)
27

Advertisement

Table of Contents
loading

This manual is also suitable for:

6es7132-6md00-0bb1

Table of Contents