Functions; Switching Cycle Counter - Siemens DQ 16x24VDC/0.5A HF User Manual

Simatic s7-1500/et 200mp digital output module
Hide thumbs Also See for DQ 16x24VDC/0.5A HF:
Table of Contents

Advertisement

2.2

Functions

2.2.1

Switching cycle counter

The function records the number of switching cycles of the output and thus the switching
cycles of a connected actuator, such as those of solenoid valves. When the specified
number of switching cycles is reached, the "Limit value warning" maintenance interrupt is
triggered, provided it is configured and enabled. When replacing the actuator, you can reset
the switching cycle counter from the user program.
When replacing modules, you have the option of pre-initializing the switching cycle counter
from the user program.
Typical areas of application:
● Recording the number of switching cycles of the connected devices, e.g. solenoid valves
or load contactors
● Predictive maintenance
Advantages
● You configure this function instead of programming.
● "Monitoring" of each individual channel is possible. You can select which outputs are
"monitored".
● You can adapt the plant configuration flexibly and individually.
● Easy to service and maintain. You can enable and disable the switching cycle counter via
the user program.
● Increase in plant availability. You can schedule actuator replacement in advance for the
next maintenance cycle.
Requirement
Firmware version as of V1.1.0 of the module.
Configuration
You configure the switching cycle counter with the following parameters:
● Switching cycle counter enabled/disabled
● Trigger maintenance interrupt when the limit is reached
● Set limit for maintenance interrupt
Digital output module DQ 16x24VDC/0.5A HF (6ES7522-1BH01-0AB0)
Manual, 06/2018, A5E35683409-AC
Product overview
2.2 Functions
13

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic s7-1500Simatic et 200mp

Table of Contents