Rectifier - ABB GPS4827 User Manual

Infinity power system
Hide thumbs Also See for GPS4827:
Table of Contents

Advertisement

Rectifier

Rectifier Specifications
Voltage Range
Frequency Range
Power Factor
AC Surge Protection: It is important that ac surges reaching rectifiers do not exceed the capacity of the rectifier internal surge
protection. Protection must be provided external to the GPS system, if necessary, to limit surge energy reaching the rectifiers.
Site surge protection must be coordinated with rectifier internal surge protection and must clamp at a lower voltage than the
rectifier internal protection. The internal protection voltage and current characteristics of the rectifiers are as follows:
Phase to Phase Voltage
320Vac(RMS)
620V maximum clamping
810Vpeak
Internal Selective High Voltage Shutdown (ISHVSD)
High Voltage Shutdown (HVSD)
Output Power
1
Output Current
Float/Boost Voltage
Total Harmonic Distortion
Regulation
Ripple
Current Limit Set Point
1.
With Galaxy Millennium Controller
2.
Factory default settings – actual range is 44 - 58Vdc
Page 85
© Copyright 2021 ABB. All rights reserved.
Electrical
Input
95-275Vac, 2-wire, single phase
45 - 66 Hz
> 0.98 at > 50% rated output
MOV Conduction Current
0A
1mA (DC test current)
100A peak
Output
1, 2
Float: 56.0Vdc Nom.
1, 2
Boost: 58.5Vdc Nom.
Float: 57.00Vdc
Output
2726W maximum
50Adc maximum from -40°C to +55°C 30Adc at +75°C
Rectifier derates at approximately
1 ampere per degree C (+55°C to +75°C)
44-58Vdc
<5% at full load
±0.5%
100 mVrms
15A-55A