Handpump; Hydraulic Test - Emerson Bettis EHO Installation, Operation And Maintenance Manual

Spring-return actuator
Table of Contents

Advertisement

Installation, Operation and Maintenance Manual
VA001-507-32 Rev. 1
4.4

Handpump

4.4.1
4.4.2
NOTE:
Handpump Isolation Valve (8)
Remove the Protective Cap. Loosen the stem retaining nut by turning counterclockwise.
Using a 5/32 inch ((4 mm)) hex wrench, turn the stem counterclockwise for open or
clockwise for close.
4.4.3
4.4.4
4.4.5
4.4.6
4.4.7
4.4.8
4.4.9
4.4.10 Check Reservoir (4) to see the hydraulic fluid is at the proper level.
NOTE:
Manual Bypass Valve (Lockable) (19) must be closed to enable any mode of operation.
Handpump Isolation Valve (8) must be open for normal operation.
4.5

Hydraulic Test

The system has been hydrostatic and function tested at the factory before shipping.
This test is to discover if any leaks have developed in the hydraulic fittings during shipment.
4.5.1
4.5.2
4.5.3
4.5.4
4.5.5
4.5.6
Set-up/Start-up Procedure
Check the Reservoir (4) to see the hydraulic fluid is at the proper level.
Close Handpump Isolation Valve (8).
Use the handle supplied with the pump to raise the pump clevis. This will draw
hydraulic fluid from the reservoir (4) into the handpump.
Pull the pump handle down to discharge the hydraulic fluid into the cylinder of the
Actuator (1). Repeat until you see the handpump is working correctly.
Repeat operating the handle until the actuator has completed its power stroke.
Push Handpump Bypass Valve (16) located on the bottom of the handpump and
pull the pump handle down, retracting the pump ram back into the pump body.
Slowly open Manual Bypass Valve (Lockable) (19) to allow the actuator to
spring-return to its Fail-Safe Position.
After the actuator has returned to its Fail-Safe Position and pressure has been
released, close Manual Bypass Valve (Lockable) (19).
Open the Handpump Isolation Valves (8) to return to automatic operation.
Open Handpump Isolation Valve (8) and ensure Manual Bypass Valve (Lockable)
(19) is closed.
Using the supplied handle, stroke Handpump (13) four or five times and stop.
Allow the unit to remain under pressure for a few minutes and check all fittings
for leakage.
If any leakage is found, release the pressure by slowly opening Manual Bypass Valve
(Lockable) (19). Repair any leakage and repeat the pressure test from step 4.4.1.
Push Handpump Bypass Valve (16), located on the bottom of the handpump, and
pull the pump handle, retracting the pump ram back into the pump body.
Open the Handpump Isolation valves (8). ((See NOTE above.))
Check Reservoir (4) to see the hydraulic fluid is at the proper level.
Section 4: Set-up/Start-up Procedure
December 2022
23

Advertisement

Table of Contents
loading

Table of Contents