Installation and user's guide
MULTICAL® 403
Kamstrup A/S · Industrivej 28, Stilling · DK-8660 Skanderborg · T: +45 89 93 10 00 · info@kamstrup.com · kamstrup.com

Advertisement

Table of Contents
loading

Summary of Contents for Kamstrup MULTICAL 403

  • Page 1 Installation and user’s guide MULTICAL® 403 Kamstrup A/S · Industrivej 28, Stilling · DK-8660 Skanderborg · T: +45 89 93 10 00 · info@kamstrup.com · kamstrup.com...
  • Page 2 MULTICAL® 403-V - Pt100 - Heat meter MULTICAL® 403-C - Pt500 - Cooling meter Battery for replacement Kamstrup type HC-993-02 (1 x D cell) Kamstrup type HC993-09 (2 x A cell) Communication Modules For an overview of available modules we refer to section 9, page 16.
  • Page 3: Table Of Contents

    9.12 Low Power Radio, inputs (In-A, In-B), 434 MHz, type HC-003-50 9.13 Low Power Radio GDPR, inputs (In-A, In-B), 434 MHz, type HC-003-51 9.14 LON TP/FT-10, inputs (In-A, In-B), type HC-003-66 9.15 Modbus RTU, inputs (In-A, In-B), type HC-003-67 10 Set-up via front keys Kamstrup A/S • 55121739_B1_GB_02.2020...
  • Page 4: General Information

    MULTICAL® 403 1 General information Please read this guide carefully before mounting the energy meter. In case of incorrect mounting, Kamstrup's guarantee obligations no longer apply. Please note that the following installation conditions must be obeyed: - Pressure stage: PN16/PN25, see marking.
  • Page 5: Mounting Of Temperature Sensors

    They can also be mounted in installations with standard tee-pieces. Kamstrup A/S can supply R½ and R¾ brass nipples that fit the short direct sensors. The short direct sensor can also be mounted directly in selected flow sensors from Kamstrup A/S.
  • Page 6: Pocket Sensor (Pl)

    The below table shows which temperature sensor types to use with which flow sensor. Flow sensor Temperature sensor Can be mounted in flow Cannot be mounted in flow sensor. sensor. DS 27.5 DS 38 Ø5.8 mm pocket 0.6-1.5 G¾B 0.6-1.5 3.5-6 G5/4B Kamstrup A/S • 55121739_B1_GB_02.2020...
  • Page 7: Mounting Of Flow Sensor

    Kamstrup flow sensors require neither straight inlet nor straight outlet to meet the Measuring Instruments Directive (MID) 2014/32/EU, OIML R75:2002 and EN 1434:2015. A straight inlet section will only be necessary in case of heavy flow disturbances before the meter.
  • Page 8: Flow Sensor Position

    This applies to temperatures up to approx. 80 °C. The flow sensor must not be exposed to pressure lower than the ambient pressure (vacuum). 3.3 Installation of MULTICAL® 403 flow sensor 90° 90° 90° 90° The flow sensor can be mounted horizontally, vertically or at an angle. Kamstrup A/S • 55121739_B1_GB_02.2020...
  • Page 9 Note: In installations where the media temperature is below the ambient temperature, MULTICAL® 403-T or 403-C must be used. At the same time, the flow sensor must not be installed with the plastic housing turned below 0°. Kamstrup A/S • 55121739_B1_GB_02.2020...
  • Page 10: Installation Examples

    Flow from the right 3.5 Humidity and condensation If there is risk of condensation, e.g. in cooling systems, a condensation-proof MULTICAL® 403, type 403-C, must be used. In case of bidirectional heat/cooling energy metering, type 403-T is used. Kamstrup A/S • 55121739_B1_GB_02.2020...
  • Page 11: Mounting The Calculator

    Note: For q 3.5 flow sensors and larger it is possible to demount the bracket from the flow sensor and use it as a wall bracket. Kamstrup A/S • 55121739_B1_GB_02.2020...
  • Page 12: Position Of Calculator

    MULTICAL® 403 4.3 Position of calculator If the flow sensor is installed in a humid or condensing environment, the calculator must be wall mounted and positioned higher than the flow sensor. Kamstrup A/S • 55121739_B1_GB_02.2020...
  • Page 13: Information Codes "Info

    V1 Air V1 wrong flow direction V1 > q for more than an hour Pulse input A, leakage in system Pulse input A, external alarm Pulse input B, leakage in system Pulse input B, external alarm Example: Kamstrup A/S • 55121739_B1_GB_02.2020...
  • Page 14: Power Supply

    The battery cannot and must not be charged and must not be short-circuited. Used batteries must be handed in for approved destruction, e.g. at Kamstrup A/S. Further details appear from document on handling and disposal of lithium batteries (5510-408).
  • Page 15: Testing Of Function

    Please also see the position of the terminals in the figure to the right: Terminal no. Standard heat and cooling measurement t1 5-6 Sensor in inlet pipe (red label) t2 7-8 Sensor in outlet pipe (blue label) Kamstrup A/S • 55121739_B1_GB_02.2020...
  • Page 16: Communication Modules

    Note that the meter factor (litres/pulse) must match the extra water meters and the configurations of inputs A and B. After delivery, the configurations of pulse inputs A and B can be changed by means of the PC program METERTOOL HCW. Kamstrup A/S • 55121739_B1_GB_02.2020...
  • Page 17: Pulse Outputs

    PC. The signal is passive and galvanically separated. In order to read data, an active converter cable, 66-99-106 (D-SUB 9F) or 66-99-098 (USB type A) is required. The converter cable must be connected as follows: Brown (DAT) White (REQ) Green (GND) Kamstrup A/S • 55121739_B1_GB_02.2020...
  • Page 18: Wired M-Bus, Inputs (In-A, In-B), Type Hc-003-20

    9.8 Wireless M-Bus, inputs (In-A, In-B), 868 MHz, type HC-003-30 The Wireless M-Bus module has been designed to be part of Kamstrup’s hand-held Wireless M-Bus Reader system, which operates within the unlicensed frequency band in the 868 MHz area. The radio module is available with either internal or external antenna.
  • Page 19: Analog Outputs 2 X 0/4

    9.12 Low Power Radio, inputs (In-A, In-B), 434 MHz, type HC-003-50 The Low Power Radio module is designed to be part of Kamstrup’s reading system or of a radio mesh network. The module is available with either internal or external antenna.
  • Page 20: Lon Tp/Ft-10, Inputs (In-A, In-B), Type Hc-003-66

    Modbus Implementation Guide V1.02. The module communicates via RS485 with speeds up to 115200 baud. The twisted shielded cables are connected to the terminals 137, 138 and 139. " The module requires that the meter is mains-supplied. Kamstrup A/S • 55121739_B1_GB_02.2020...
  • Page 21: Set-Up Via Front Keys

    METERTOOL HCW. Furthermore, all modules can adjust the clock. *** q can only be changed in meters configured as meter type 6. Upon attempts to access this menu in meters configured with other country codes the display shows the message ”Off”. Kamstrup A/S • 55121739_B1_GB_02.2020...
  • Page 22 MULTICAL® 403 Kamstrup A/S • 55121739_B1_GB_02.2020...
  • Page 23 Activate to view the max value of the current year followed by the max value of the current month. Display readings are based on DDD-code 210. At kamstrup.com you find a selection of interactive user guides based on other DDD-codes.
  • Page 24 User Guide MULTICAL® 403 Kamstrup A/S · Industrivej 28, Stilling · DK-8660 Skanderborg · T: +45 89 93 10 00 · info@kamstrup.com · kamstrup.com...