Page 2
MULTICAL® 403-W - Pt500 MULTICAL® 403-T - Pt500 MULTICAL® 403-V - Pt100 Battery for replacement Kamstrup type 403-0000-0000-200 (1 x D-cell) Kamstrup type 403-0000-0000-100 (2 x AA-cell) Communication Modules For an overview of available modules we refer to section 9, page 18.
9.4 Data + pulse inputs, type HC-003-10 9.5 Data + pulse outputs, type HC-003-11 9.6 M-Bus + pulse inputs, type HC-003-20 9.7 M-Bus + pulse outputs, type HC-003-21 9.8 Wireless M-Bus + pulse inputs, type HC-003-30 10 Set-up via front keys Kamstrup A/S • 55121739_A4_GB_11.2017...
MULTICAL® 403 1 General information Please read this guide carefully before mounting the energy meter. In case of incorrect mounting, Kamstrup's guarantee obligations no longer apply. Please note that the following installation conditions must be obeyed: - Pressure stage: PN16/PN25, see marking. The meter marking does not apply to enclosed accessories.
They can also be mounted in installations with standard tee- pieces. Kamstrup A/S can supply R½ and R¾ brass nipples that fit our short direct sensors. The short direct sensor can be also be mounted directly in selected flow sensors from Kamstrup A/S.
Push the plastic sleeve on the sensor cable into the sensor pocket and secure the cable by means of the enclosed M4 sealing screw. Fasten the screw with your fingers only. Seal the pockets using seal and locking wire. Kamstrup A/S • 55121739_A4_GB_11.2017...
The below table shows which temperature sensor types to use with which flow sensor. Flow sensor Temperature sensor Can be mounted in flow Cannot be mounted in flow sensor. sensor. DS 27.5 DS 38 Ø5.8 mm pocket 0.6-1.5 G¾B 0.6-1.5 3.5-6 G5/4B Kamstrup A/S • 55121739_A4_GB_11.2017...
3.1 Mounting of couplings, and short direct sensor in MULTICAL® 403 flow sensor The short direct sensor from Kamstrup may be installed in PN16 installations only. The blind plug which is mounted in the MULTICAL® 403 flow sensor from the factory can be used in connection with both PN16 and PN25.
1.5 bar at q (nominal flow) and minimum 2.5 bar at q (maximum flow). This applies to temperatures up to approx. 80 °C. The flow sensor must not be exposed to lower pressure than ambient pressure (vacuum). Kamstrup A/S • 55121739_A4_GB_11.2017...
3.3 Mounting of MULTICAL® 403 flow sensor 90° 90° 90° 90° The flow sensor can be mounted horizontally, vertically, or at an angle. 90° 90° The flow sensor should be mounted at 0° and can be turned downwards to 90°. Kamstrup A/S • 55121739_A4_GB_11.2017...
Flow from the right Flange meter: Flow from the left Flow from the right 3.5 Humidity and condensation If there is risk of condensation, e.g. in cooling systems, a condensation-proof MULTICAL® 403, type 403-T, must be used. Kamstrup A/S • 55121739_A4_GB_11.2017...
Note: For q 3.5 flow sensors and larger it is possible to demount the bracket from the flow sensor and use it as a wall bracket. Kamstrup A/S • 55121739_A4_GB_11.2017...
MULTICAL® 403 4.3 Position of calculator If the flow sensor is installed in a humid or condensing environment, the calculator must be wall mounted and positioned higher than the flow sensor. Kamstrup A/S • 55121739_A4_GB_11.2017...
V1 Air V1 wrong flow direction V1 > q for more than an hour Pulse input A, leakage in system Pulse input A, external alarm Pulse input B, leakage in system Pulse input B, external alarm Example: Kamstrup A/S • 55121739_A4_GB_11.2017...
The battery cannot and must not be charged and must not be short-circuited. Used batteries must be handed in for approved destruction, e.g. at Kamstrup A/S. Further details appear from document on handling and disposal of lithium batteries (5510-408).
230 VAC Supply cable Max. Fuse 2 x 0.75 mm (accessory from Kamstrup A/S) 230 VAC 2 x 1.0 mm 10 A This module is used when the meter is supplied directly by the mains.
Please also see the position of the terminals in the figure to the right: Terminal no. Standard heat and cooling measurement t1 5-6 Sensor in inlet pipe (red label) t2 7-8 Sensor in outlet pipe (blue label) Kamstrup A/S • 55121739_A4_GB_11.2017...
The pulse duration is ordered at 32 ms. or 100 ms. After delivery the pulse duration can be changed by means of the PC program METERTOOL HCW. The resolutions of the pulse outputs always follow the least significant digit displayed for energy and volume respectively. Kamstrup A/S • 55121739_A4_GB_11.2017...
The module is connected to an M-Bus master via terminals 24 and 25 using a twisted pair. The polarity is without importance for the functionality. The module is powered by the connected master. Kamstrup A/S • 55121739_A4_GB_11.2017...
9.8 Wireless M-Bus + pulse inputs, type HC-003-30* The wireless M-Bus module has been designed to form part of Kamstrup’s hand-held Wireless M-Bus Reader system, which operates within the unlicensed frequency band in the 868 MHz area. The radio module is available with either internal or external antenna.
METERTOOL HCW. Furthermore, all modules can adjust the clock. *** q can only be changed in meters configured as meter type 6. Upon attempts to access this menu in meters configured with other country codes the display shows the message ”Off”. Kamstrup A/S • 55121739_A4_GB_11.2017...
Page 23
Activate to view the max value of the current year followed by the max value of the current month. Display readings are based on DDD-code 210. At kamstrup.com you find a selection of interactive user guides based on other DDD-codes.