Supp. for ULTRAFLOW installation guide no. 5 511-704 ® Electrical connection PULSE DIVIDER ULTRAFLOW PULSE DIVIDER MULTICAL ® ® Blue (GND)/11A Red (supply)/9A Yellow (signal)/10A ULTRAFLOW PULSE DIVIDER MAXICAL III/11 EVL ® Blue (GND)/11A Red (supply)/9A Yellow (signal)/10A The use of long signal cables requires careful handling in connection with installation.
Pulse output – Passive (STANDARD) 66-99-607 PULSE DIVIDER – Passive Type: Open collector. 2- or 3-wire connection via the integrated pull-up resistance of 33 k Cable length, flow meter: Max. 10 m Cable length, PULSE DIVIDER: Dependent on the calculator...
Flow diagram of a PULSE DIVIDER re-configured to an active output Connection example for PULSE DIVIDER re-configured to an active output Re-configuration Re-configuration of the PULSE DIVIDER from passive to active pulse output is made by adding 2 pcs. 820 1/8 W resistances to the connection print. Please refer to below drawing.
Tabels for PULSE DIVIDER Tabel with a pulse duration of 100 ms. ULTRAFLOW ® Pulse Divider ® ULTRAFLOW Pulse Divider Meter Meter Meter Meter factor factor Divider factor factor Divider [m3/h] [m3/h] [Pulses/l] [l/Pulse] [Pulses/l] [l/Pulse] 1500 1000 1250 1250 1000 1000 2500...
Page 7
Divider Meter factor [l/pulse] Divider [pulses/l] 0.25 1000 0.25 Table on the use together with Kamstrup EVL and 11 EVL, and 11 EVL, PULSE DIVIDER PULSE DIVIDER U L T R A F L O W 50 ms 100 ms...