5 Information codes "INFO"

MULTICAL® 403 constantly monitors a number of important functions. If a serious error occurs in
the measuring system or the installation, a flashing "INFO" will appear in the display. The "INFO"-
field keeps flashing as long as the error is present no matter which reading you choose. The
"INFO"-field is automatically switched off when the error has been corrected. The info code can be
displayed in in TECH loop reading 2-017-00, for indication of current errors in MULTICAL® 403. The
info code consists of 8 digits and each functionality has its own digit dedicated to the indication
of relevant information. For instance all information concerning temperature sensor t1 is shown in
the display as the second digit from the left.
Display digit
1
2
3
Info
t1
t2
1
2
9
1
1
2
2
9
9
Example:
1
0
2
Kamstrup A/S • 55121739_B1_GB_02.2020
4
5
6
7
0
V1
0
In-A In-B
3
4
6
8
9
0
0
0
9
8
No voltage supply
Low battery level
External alarm (e.g. via KMP)
t1 Above measuring range or switched off
t2 Above measuring range or switched off
t1 Below measuring range or short-circuited
t2 Below measuring range or short-circuited
Invalid temperature difference (t1-t2)
V1 Air
V1 wrong flow direction
V1 > q
for more than an hour
s
Pulse input A, leakage in system
Pulse input A, external alarm
8
Pulse input B, leakage in system
9
Pulse input B, external alarm
0
MULTICAL® 403
Description