4. For CPE302/305-Bxxx:
a. Visually inspect the module to be sure it is properly seated.
b. Tighten the two captive screws located in the module's
5. For CPE310-Bxxx:
a. Ensure the release lever on the bottom of the module snaps
b. Visually inspect the module to be sure it is properly seated.
6. Mount the Energy Pack on the left side of the module in slot 0 of the rack
(typically a power supply).
a. Engage the Energy Pack's mounting hooks (at the top) on the frame
of the leftmost module.
b. Rotate the bottom of the Energy Pack into place, engaging the
bottom hooks. The latch will snap into place.
c.
Connect cable IC695CBL001 from the connector on the bottom of
the Energy Pack to the corresponding connector on the bottom of
CPE302/305/310-Bxxx.
7. If required, connect the CPE302/305/310-Bxxx to the Ethernet network.
8. Apply power to the rack.
Note:
When the Energy Pack is powered up for the first time or is
in a system that has been powered down long enough to
completely discharge the Energy Pack, it may require a few
seconds for it to charge to its operating level. The CPU's
STATUS LED will blink green during this time.
10
PACSystems™ RX3i IC695CPE302/305/310-Bxxx
bottom bracket to fasten the bottom to the backplate.
Tighten screws using a #1 Phillips screwdriver. Tighten to
0.7 N-m (6 in-lbs.).
into place in the bottom module retainer of the backplane.
GFK-3249B