INSTRUCTION SHEET - HS6E Series
INSTRUCTION SHEET
Original Instructions
Solenoid Type Safety Switch
HS6E Series
Confirm that the delivered product is what you have ordered.
Read his instruction sheet to make sure of correct operation.
S A F E T Y P R E C A U T I O N S
In this operating instruction sheet, safety precautions are categorized to Warning and
Caution:
WARNING
Warning notices are used to emphasize that improper operation may cause severe
personal injury or death.
CAUTION
Caution notices are used where inattention might cause personal injury or damage to
equipment.
1
Type
Circuit Code
Main
Door Monitor Lock Monitor
Circuit
Circuit
L : 1NC+1NC
2NC
M : 1NC+1NC
2NC
N : 1NC+1NC
1NC, 1NO
P : 1NC+1NC
1NC, 1NO
VL :
3NC
VM :
3NC
VN :
2NC, 1NO
VP :
2NC, 1NO
Solenoid Voltage / Lock Mechanism
4 : 24V DC / Spring Lock
7Y : 24V DC / Solenoid Lock
CAUTION
Solenoid lock type
• This safety switch is designed to lock the actuator while the solenoid is energized
and to release it when deenergized.
• When the power to the solenoid is interrupted by accident, such as disconnection,
the lock is released before a machine stops ompletely. Then, the worker may be
exposed to hazards.
• This safety switch can be used only for limited applications which do not especially
need to be locked for safety.
2
Specifications and Ratings
Applicable Standards
Standards for Use
Interlocking device Type
/the level of coded
Applicable Directives
Condition
Operating Temperature
Operating Humidity
Pollution degree
Altitude
Impulse withstand voltage ‹Uimp›
Rated Insulation voltage ‹Ui›
Thermal Current ‹Ith›
Contact Ratings
‹Ue, Ie›
(Main circuit ・
Door monitor circuit)
* In order to verify if the product
you are interested in is certified
with the S mark, please check
the following section on our
website: "List of type numbers
certified with the S mark"
H S 6 E - L 4 4 B 0 1 - G
Pilot Light Color
G : Green
Circuit
1NO
1NC
1NO
1NC
Housing Color
B : Black
1NC, 1NO
2NC
Indicator Voltage
4 : 24V DC
1NC, 1NO
2NC
EN ISO / ISO14119, GB14048.5
IEC60947-5-1, EN60947-5-1
GS-ET-19, UL508, CSA C22.2 No.14
IEC60204-1, EN60204-1
Type 2 Interlocking device
/ low level coded actuator (EN ISO / ISO14119)
Machinery Directive, Low Voltage Directive
-25 to +50°C (no freezing)
45 to 85%RH(no condensation)
3(Inside 2)
2,000m maximum
1 5kV(Main,Lock monitor circuit)
2 5kV(Door monitor circuit)
0.5kV(Between ground and LED,solenoid circuit)
150V(Main,Lock monitor circuit)
300V(Door monitor circuit)
30V(Between ground and LED,solenoid circuit)
-25°C ≤ Operating temperature < 35°C
2.5A (≤ 2 circuits)
1.0A (≥ 3 circuits)
35°C ≤ Operating temperature ≤ 50°C
1.0A (1 circuit)
0.5A (≥ 2 circuits)
30V
125V
Main
Resistive load
-
Circuit,
(AC-12)
Look
AC
Inductive load
monitor
-
(AC-15)
circuit
Solenoid Type Safety Switch
Class of Protection
Operating Frequency
Operating Speed
B10d
Mechanical Durability
Electrical Durability
Shock Resistance
Vibration Resistance
Actuator Tensile Strength
when Locked
Direct Opening Travel
Direct Opening Force
Contact Resistance
Degree of Protection
Conditional short circuit current
Short-circuit Protective Device
Rated Operating Voltage
Rated Current
Turn ON Voltage
Turn OFF Voltage
Rated Operating Voltage
Light Source
Illumination Color
Rated Power Consumption
Ratings approved by safety agencies
(1) TÜV rating
Main circuit, Look monitor circuit
AC-15 125V/1A
DC-13 125V/0.22A
DC-13 30V/1A
Door monitor circuit
AC-15 240V/0.75A
DC-13 250V/0.27A
DC-13 30V/2.3A
(3) CCC rating
Main circuit, Look monitor circuit
AC-15 125V/1A
DC-13 30V/1A
Door monitor circuit
AC-15 240V/0.75A
DC-13 30V/2.3A
*1 Basic insulation of 2.5kV, 1.5kV impulse withstand voltage is ensured between
different contact circuits and between contact circuits and LED or solenoid in he
enclosure. When both SELV (safety extra low voltage) or PELV (protective extra
low voltage) circuits and other circuits (such as 230V AC circuits) are used for he
solenoid power and contact circuits at the same time, the SELV or PELV
requirements are not met any more.
*2 The actuator locking strength is rated at 500N of static load. Do not apply a load
higher than the rated value. When a higher load is expected to work on the
actuator, provide an additional system consisting of another safety switch without
lock (such as the HS6B/HS7A safety switch) or a sensor to detect door opening
and stop the machine.
*3 F1max. is maximum force. The actuator's guard-locking force Fzh is calculated in
accodance with GS-ET-19:
Fzh
*4 Make sure that a fast acting fuse for short-circuit protection trips before
overheating of the wires.
250V
2A
-
1A
-
Resistive load
(DC-12)
DC
Inductive load
(DC-13)
Resistive load
Door
(AC-12)
monitor
AC
circuit
Inductive load
(AC-15)
Resistive load
(DC-12)
DC
Inductive load
(DC-13)
Class II (IEC61140) *1
900 operations/hour
0.05 to 1.0 m/s
2,000,000 (EN ISO 13849-1 AnnexC Table C.1)
1,000,000 operations minimum. (GS-ET-19)
100,000 operations minimum.
(900 operations / hour,
AC-12 125V 2A, DC-12 125V 0.4A)
1,000,000 operations minimum.
(900 operations / hour,
24V AC/DC 0.1A Resistive Load)
Operating Extremes: 100m/s
Operating Extremes:10 to 55 Hz, half amplitude 0.35mm
Damage Limits: 30 Hz, half amplitude 1 5mm
Fzh=500N minimum
F1max.=650N minimum (GS-ET-19) *2, *3
(Fzh=100N minimum: HS9Z-A62 actuator)
8 mm minimum
60 N minimum
300 m Ω maximum (initial value, 1m cable)
IP67 (IEC60529)
NEMA Type12 (operating temp. -25 to 45°C)
50A (250V)
Use 250V / 10A fast acting type fuse
DC24V 100% duty cycle
110 mA (solenoid 100mA, LED 10mA : initial value)
Rated voltage x 85% maximum (at 20°C)
Rated voltage x 10% minimum (at 20°C)
DC24V 100% duty cycle
LED
Green
Approx. 2.7W
(2) UL, c-UL rating
Main circuit, Look monitor circuit
1A, 125V ac, Pilot Duty
0.22A, 125V dc, Pilot Duty
1A, 30V dc, Pilot Duty
Door monitor circuit
C300 0.75A, 240V ac, Pilot Duty
Q300 0.27A, 250V dc, Pilot Duty
(4) KOSHA rating
Main circuit, Look monitor circuit
AC-15 125V/1A
DC-13 125V/0.22A
Door monitor circuit
AC-15 240V/0.75A
DC-13 250V/0.27A
maximum force (F1max.)
=
Safety coefficient (=1.3)
-
2016.08
B-1906-1(0)
2A
0.4A
-
1A
0.22A
-
-
2.5A
1.5A
-
1.5A
0.75A
2.5A
1.1A
0.55A
2.3A 0.55A 0.27A
, Damage Limits: 1,000m/s
2
2
*4
( 1 / 6 )

Advertisement

loading

Summary of Contents for IDEC HS6E Series

  • Page 1 INSTRUCTION SHEET - HS6E Series 2016.08 Solenoid Type Safety Switch B-1906-1(0) Resistive load 0.4A (DC-12) Inductive load 0.22A (DC-13) INSTRUCTION SHEET Resistive load Door 2.5A 1.5A (AC-12) monitor ※ circuit Inductive load Original Instructions 1.5A 0.75A (AC-15) Solenoid Type Safety Switch Resistive load 2.5A...
  • Page 2: Mounting Examples

    INSTRUCTION SHEET - HS6E Series 2016.08 Solenoid Type Safety Switch B-1906-1(0) • After removing the actuator stop, ensure that the actuator is installed within the Mounting Examples tolerances shown below. From he entry slot center of the safety switch (*5, 6) : ±1.0mm •...
  • Page 3: Contact Operation

    Otherwise the safety switch is damaged. Make sure that all screws are installed, otherwise the waterproof capability is lost. • HS6E Series Safety Switches are Type 2 low-level coded interlocking devices (EN ISO / ISO14119). The following system installation & mounting instructions are EN ISO / ISO14119 requirements to prevent function failure from the interlock switch.
  • Page 4: Operation Cycle

    INSTRUCTION SHEET - HS6E Series 2016.08 Solenoid Type Safety Switch B-1906-1(0) CAUTION Wiring *9 The Actuator is inserted, and HS6E is locked. Wiring Colored Insulator • Cable specifications • Contact operation is based on the condition that the actuator is inserted into the UL style 2464, 12c×No.22AWG, (80°C 300V)
  • Page 5 INSTRUCTION SHEET - HS6E Series 2016.08 Solenoid Type Safety Switch B-1906-1(0) Example of wiring Diagram realizing Safety Category Example of a circuit diagram for Safety Category 3 Example of a circuit diagram for Safety Category 4 (attainable PL = d)
  • Page 6 When installed on Heselstuecken 8, D-22453 Hamburg, Germany the door (5) DECLARATION OF CONFORMITY We, IDEC CORPORATION 2-6-64, Nishimiyahara Yodogawa-ku,Osaka 532-0004, Japan declare under our sole responsibility that the product: Description: Safety Switch Model No: HS6E to which this declaration relates is in conformity with the EC Directive on the following standard(s) or other normative document(s).

This manual is also suitable for:

Hs6e-l seriesHs6e-m seriesHs6e-n seriesHs6e-p seriesHs6e-vl seriesHs6e-vm series ... Show all