INSTRUCTION SHEET - HS1T Series
INSTRUCTION SHEET
Original Instructions
Solenoid Type Safety Switch
HS1T Series
Thank you for purchasing this IDEC product. Confirm that the delivered product is
what you have ordered. Read his instruction sheet to make sure of correct operation.
S A F E T Y P R E C A U T I O N S
In this operation instruction sheet, safety precautions are categorized in order of
importance to Warning and Caution :
WARNING
Warning notices are used to emphasize that improper operation may cause severe
personal injury or death.
CAUTION
Caution notices are used where inattention might cause personal injury or damage to
equipment.
1
Type
H S 1 T- V D 4 4 Z L M - G
Solenoid Voltage / Lock Mechanism
4 : 24V DC / Spring Lock
7Y : 24V DC / Solenoid Lock
Pilot Light Rated Voltage
4 : 24V DC
Head material
Z:Metal
Circuit Code
Contact Congifiguration
Main
Door monitor
Lock monitor
circuit
circuit
circuit
-
1NC
1NC
-
2NC
-
1NC,1NO
-
-
2NC
-
1NC,1NO
1NC,1NO
-
1NC,1NO
2NC
-
2NC
1NC,1NO
-
2NC
2NC
-
3NC
1NC
-
2NC,1NO
1NC
-
1NC
3NC
-
1NC
2NC,1NO
-
1NO
3NC
-
1NO
2NC,1NO
1NC+1NC
-
1NC+1NC
-
1NO
1NC
-
-
1NC,1NO
1NC+1NC
1NO
1NO
1NC+1NC
1NO
1NC
1NC+1NC
1NC
1NO
1NC+1NC
1NC
1NC
1NC+1NC
2NC
1NC+1NC
1NC,1NO
1NC+1NC
-
2NC
1NC+1NC
-
1NC,1NO
-
1NO
1NC,1NO
-
1NO
2NC
-
1NC
1NC,1NO
-
1NC
2NC
-
2NC
1NC
-
1NC,1NO
1NC
-
-
3NC
-
-
2NC,1NO
*1 Only type No. on √ mark are supplied
as standard.
Contact IDEC for the other if required.
Indicator Color
G : Green
Rear Unlock Button
Blank : Without Rear Unlock Button
L : Rear Unlock Button
Standard type
□
□
HS1T-
HS1T-
44ZM-G
44ZLM-G
XD
√
-
-
XF
-
-
-
XG
-
-
XH
√
√
VA
√
√
VB
-
-
VC
√
-
VD
√
√
VF
-
-
VG
-
-
VH
√
-
VJ
√
-
VW
√
-
VX
√
-
-
DD
√
-
XB
-
-
XJ
-
-
A
-
-
B
-
-
C
-
-
D
-
-
-
F
-
-
-
G
-
-
H
-
-
J
-
-
TA
-
-
TB
-
-
TC
-
-
TD
-
-
TF
-
-
TG
-
-
TH
-
-
TJ
-
-
Spring Lock Type Solenoid Lock Type
Rear Unlock Button
Solenoid Type Safety Switch
CAUTION
Solenoid lock type
• This safety switch is designed to lock the actuator while the solenoid is energized
and to release it when deenergized.
• When the power to the solenoid is interrupted by accident, such as disconnection,
the lock is released before a machine stops ompletely. Then, the worker may be
exposed to hazards.
• This safety switch can be used only for limited applications which do not especially
need to be locked for safety.
2
Specifications and Ratings
Applicable Standards
Standards for Use
Interlocking device Type
/ the level of coded
Applicable Directives
Operating Condition
Inpulse withstand voltage
‹Uimp›
Raed Insulation voltage‹Ui›
Thermal Current‹lth›
Thermal Current ‹ h›
Contact Ratings
(Reference Values)
‹Ue, Ie›*2
Class of Protection
Operating Frequency
Operating Speed
B10d
Mechanical durability
Electrical Durability
□
HS1T-
7Y4ZM-G
Shock Resistance
√
Vibration Resistance
-
-
Actuator Tensile Streng h
√
when Locked
√
-
Direct Opening Travel
-
√
Direct Opening Force
√
Contact Resistance
√
Degree of Protection
-
Condi ional short circuit
-
current
-
Short-circuit Protective
-
Device
-
Rated Operating Voltage
Rated Current
-
Turn ON Voltage
-
Turn OFF Voltage
-
Rated Power Consumption
-
Rated Operating Voltage
-
Rated Current
-
Light Source
-
Illumination Color
-
Weight
-
*2 Ratings approved by safety agencies
-
(1)TÜV/CCC rating
-
-
(2)UL , c-UL rating
-
-
-
-
-
-
*3 Basic insulation of 2.5kV impuise withstand circuits and between contact circuit
SELV(safety extra low voltage) or circuits (such as 230V AC circuits) at the same
time, the SELV or PELV arequirements are met any more.
*4 The actuator locking strength is rated at 5000N of static load. Do not apply a load
higher than the rated value. When a higher load is expected to work on the
actuator, provide an additional system consisting of another safety switch without
lock (such as the HS5D safety switch) or a sensor to detect door opening and stop
the machine.
EN ISO / ISO14119, IEC60947-5-1, EN60947-5-1,
GS-ET-19,UL508, CSA C22.2 No.14, GB/T 14048. 5
IEC60204-1/EN60204-1
Type 2 Interlocking device
/ low level coded actuator (EN ISO / ISO14119)
Low Voltage Directive, Machinery Directive
Operating Temperature
-25 to +55°C (no freezing)
Operating Humidity
20 to 95%RH (no condensation)
Pollution Degree
3 (Inside 2)
Altitude
2000m maximum
2.5kV (Between ground and LED, solenoid circuit : 0.5kV)
250V (Between ground and LED, solenoid circuit : 30V)
2.5A
30V
AC Resistive load (AC12)
Inductive load (AC15)
DC Resistive load (DC12)
2.0A
Inductive load (DC13)
1.0A
Class II (IEC61140) *3
900 opera ions/hour
0.05 to 1.0 m/s
2,000,000 (ISO 13849-1 Annex C Table C.1)
2,000,000 operations minimum (GS-ET-19)
The Rear Unlock Button: 3000 operations
□
minimum (Type HS1T-
L)
100,000 operations min. (AC-15 250V/0.75A)
2,000,000 operations min. (AC/DC 24V 100mA)
(900 operations / hour)
Operating Extremes: 100m/s
, Damage Limits: 1000m/s
2
Operating Extremes:10 to 55 Hz, half amplitude 0.35mm
Damage Limits: 30 Hz, half amplitude 1.5mm
Fzh=5,000N minimum
F1max=6500N minimum (GS-ET-19) *4, *5
12 mm minimum
120N minimum
50 mΩ maximum (initial value)
IP67 (IEC60529) , Type 4X Indoor Use Only
50A(250V)
Use 250V / 10A fast acting type fuse *6
DC24V 100% duty cycle
200 mA (initial value)
Rated voltage x 85% maximum (at 20°C)
Rated voltage x 10% minimum (at 20°C)
Approx. 5W
DC24V 100% duty cycle
10 mA
LED
Green
Approx. 450g
AC-15 250V/0.75A
DC-13 30V/1.0A
0.75A, 250V ac, Pilot Duty
1A, 30V dc, Pilot Duty
The M20 threaded opening must be filled by a Listed or
Recognized Component Liquid-Tight Flexible Cord Fitting
in order to maintain the Tye 4X Indoor use only rating.
2019.07
B-2048-1(1)
125V
250V
-
2.5A
1.5A
-
1.5A
0.75A
0.4A
0.2A
0.22A
0.1A
2