Maintenance History - Magnetek IMPULSE G+ 4 Series Technical Manual

Adjustable frequency/vector crane controls
Hide thumbs Also See for IMPULSE G+ 4 Series:
Table of Contents

Advertisement

5.8.3 Maintenance History

Parameter
Display
O03-01
Elapsed Time Set
O03-02
Elapsed Time Run
0
Power-On Time
1
Running Time
O03-03
Fan ON Time Set
O03-05
BusCap Maint Set
O03-09
IGBT Maint Set
O03-11
Fault Data Init
0
No Reset
1
Reset
O03-12
kWh Monitor Init
0
No Reset
1
Reset
O03-14
Count Hist Clear
0
No Reset
1
Reset Runs
2
OL/LC Count Clr
3
Both Count Clr
Table 5-109: Maintenance History Parameter Settings
Cumulative operation time of the VFD in units
of 10 hours. Cumulative time can be viewed
using monitor Cumulative Operation Time
(U04-01). A setting of 30 = 300 hours
How the cumulative timer will keep track of
the total operation time.
Logs power-on time
Logs operation time when the VFD output is
active.
Fan Operation Time monitor (U04-03) in units
of 10 hours. A setting of 30 = 300 hours
Maintenance Monitor for the capacitors. See
U04-05 to check when the capacitors may
need to be replaced.
Maintenance Monitor for the IGBTs. See U04-
07 for IGBT replacement times.
Fault Trace (U02-xx) and Fault History (U03-
xx) reset.
Not cleared
Resets the U02.xx and U03.xx fault history
Reset the monitor data (U04-10 and U04-11).
Not cleared.
Resets the U04-10 and U04-11 power meter.
Determines which counter will be cleared.
After counters are cleared, initial value (O03-
14) is set to 0.
Not cleared.
Clears run command counters (U03-21 and
U03-22).
Clears OL/LC Counters (U03-23).
Clears Runs and OL/LC Counters.
Function
IMPULSE•G+/VG+ Series 4 Technical Manual
Range
Default
0–9999 x 10 hr
0
0, 1
1
0–9999 x 10 hr
0
0–150%
0
0–150%
0
0, 1
0
0, 1
0
0–3
0
November 2022
Page 180