Eaid - Halma Ampac EV3000 Installation & Commissioning

Emergency warning & intercommunications system
Table of Contents

Advertisement

11.4 EAID

If EAID's are cabled to the main equipment they will be connected to the FACP input connection board.
EAID's are connected to the OWIS and not the Fire System. This means that the manual operation of
an EAID will trigger the Emergency Warning System and NOT indicate on the Fire System or signal the
Fire Services.
IF the EAID is in close proximity to a WIP, then wiring can be reduced by connecting the EAID to the
WIP as shown below. Wiring in this manner requires that the following criterion is met.
➢ Cabling from the WIP to the ECP must be by fire rated two-core cable.
➢ No spurs or T junctions, cables must be a single run come individual lines.
➢ EAID must be between ECP and WIP as shown below (2 wire).
The following units are only suitable for connection to the 2 Wire TS004 AMPAC EV3000 Systems
EAID (213-0068)
EIS TERMINATION BOARD (API-627)
NOTE:FIT LK1 IF
EAID NOT FITTED
WIP 2 WIRE (219-0015)
NOTE: REMOVE LK1 IF
EAID FITTED
WIP 2 WIRE (219-0015)
TB12
TB12
TB12
TB12
TB12
TB12
TB12
TB12
TB12
TB12
TB12
TB12
TB12
TB12
TB12
TB12
TB12
TB12
TB12
TB12
TB12
TB12
TB12
TB12
Figure 27: ECP to EAID to WIP Wiring
MAN1813-9
To remote buzzer
41