Field Wiring - Halma Ampac EV3000 Installation & Commissioning

Emergency warning & intercommunications system
Table of Contents

Advertisement

Supported strobe types:
➢ VAD (NEW) (4107-11**)
➢ XENON (208-0011)
➢ SONOS (208-0063, 208-0066)
➢ LED STROBES (4107-1005,4107-1006)

10.5.3 Field Wiring

The following table details visual load, wire size and length of cable runs for the LED and XENON
strobes.
For LED strobes – Max 40 per circuit
No.
of
1.0mm
Devices
Wiring
10
921m
20
460m
30
307m
40
230m
For XENON strobes – Max 16 per circuit
No.of
1.0mm
devices
Wiring
4
331m
8
166m
12
110m
16
83m
For VAD Strobes – UNIVERSAL VISUAL OUTPUT BOARD
No.
of
1.0mm
Devices
Wiring
10
444m
20
222m
30
148m
40
111m
2
2
Field
1.5mm
Field
Wiring
1377m
689m
459m
344m
2
2
Field
1.5mm
Field
Wiring
496m
248m
165m
124m
2
2
Field
1.5mm
Field
Wiring
620m
310m
207m
155m
2
2.5mm
Field
4.0
Wiring
Field Wiring
2249m
3615m
1125m
1808m
750m
1205m
562m
904m
2
2.5mm
Field
4.0mm
Wiring
Wiring
810m
1301m
405m
651m
270m
434m
202m
325m
2
2.5mm
Field
4.0
Wiring
Field Wiring
1124m
562m
375m
281m
MAN1813-9
2
2
mm
6.0mm
Field
Wiring
5411m
2706m
1804m
1353m
2
2
Field
6.0mm
Field
Wiring
1948m
974m
650m
487m
2
2
mm
6.0mm
Field
Wiring
33

Advertisement

Table of Contents
loading

Table of Contents