4. When any of the WIP handsets are taken off the cradle, a connection is made and the WIP
select indicator at the ECP goes steady. Similarly as more WIP handsets are taken off the
cradle, their respective select indicators at the ECP go steady.

8.4.7 Completing The All Call

Replacing the ECP handset on its cradle i.e.: hanging up, will cancel the ALL CALL operation. Each WIP
will be returned to the confidence tone.

8.4.8 EIS Controlling ECP

With the EWS in auto any ECP can be in control of the EIS by simply lifting the WIP handset at that ECP
from its cradle. However, when an EWS is switched to the manual position it then has control of the
EIS.
Again the MECP can override an SECP to take control of the EIS.
8.4.9 Zone Labelling - Refer to Appendix A

8.4.10 Remote Paging Console

The Remote Paging Console (RPC) has been designed to provide PA. facilities at locations which may
be remote from the E.C.P.
The RPC consists of a sloping front console with an alphanumeric keypad and a gooseneck type
microphone. A 3 digit seven segment display is used to display the selected subzone(s) and there are
3 LED indicators for power, system busy and a press to talk indicator which verifies the operation of
the push to talk (PTT) switch.
OPERATING INSTRUCTIONS
When the system is powering up the LED display will read In1. After the system powers up the LED
display will be blank.
If the system busy LED is on, or the system is powering up, the RPC cannot be used. The system busy
LED will be or if any other RPC is using the system or if the EWS system is activated at either the MECP
or an SECP.
Note 1. When paging is in progress, fault monitoring on the amplifiers is inhibited.
Note 2. If the EWS overrides the RPC's, the RPC's are disconnected and the system busy LED's are
turned on and the buzzer sounds for 3 seconds.
ZONE SELECTION
The RPC can be configured to access EWS zones as follows:
1.
Subzones
2.
Groups
3.
All Call
SUBZONE SELECTION
To select a subzone, key in the required No. and press 'ENTER/CLEAR' e.g. to select subzone 4, press 4
followed by 'ENTER/CLEAR'.
The LED display will show 4 which will flash until the RPC has control of the EWS.
these may be selected zones or parts of zones of the EWS.
these may be groups of subzones.
this is used to select all subzones configured to a particular RPC.
MAN1813-9