Field Wiring - Halma Ampac EV3000 Installation & Commissioning

Emergency warning & intercommunications system
Table of Contents

Advertisement

Figure 16B: BRDEV3FTB2 100V Line Termination Board with Filters

10.4.3 Field Wiring

The following table details audio load, wire size and length of cable runs.
Calculations are based on a 1 dB of loss (approx. 10V attenuation at the end of the cable run)
Amp Size
Load
Impedance
40Watt
250Ω
120Watt
83.3Ω
240Watt
41.7Ω
Max capacitance must be below 100nF and max inductance must be below 1mH
2
2
1.0mm
1.5mm
Field
Field
Wiring
Wiring
760m
1136m
253m
379m
127m
189m
2
2.5mm
4.0
mm
Field
Field
Wiring
Wiring
1855m
2982m
618m
994m
309m
497m
MAN1813-9
2
2
6.0mm
Field
Wiring
4464m
1488m
744m
30