Night Mode; Communication With Controller; Definition Of Abbreviation Displayed In The Controller - LAMINOX KING HEAT 6 User Manual

Dc inverter multifunctional air to water heat pump
Table of Contents

Advertisement

E51-57
E58
Ambient temperature exceeds lower limit
E59-98
Reserved
E99
Inverter model communication failure

5.4 Night mode

(1) Night mode valid or not is up to parameter P17. If the data is set 0, means off, 1
means on. The night mode starting time is decided by data P16. Ending time is
decided by data P17.
(2) With night mode, hot water mode will run with the current setting temp +3° C,
room heating run with current setting -2°C. Room cooling run with current
setting +2°C. Outdoor fan runs at low speed.

5.5 Communication with controller

Controller is connected with heat pump RS485-1 by 4 wires, (must in order) max 100m.

5.6 Definition of abbreviation displayed in the controller

Tr
Ts
To
Ts
Td
T out
T in
Tc
Ty
Outdoor temp.
Room temp.
Ps
Pd
P
A
HZ
TH
TL
TIPM
Tt
T out
T in
T6
ambient temperature <【 P82 】
Main board and inverter board Communication error
Displayed in《main interface》
Room temperature
Room temperature setting
Ambient temperature
Displayed in《refrigerant circuit》
Suction temperature
Discharge temperature
Water outlet temperature
Water inlet temperature
Coil temperature
Tube temperature of heat exchanger
Outdoor temperature
Room temperature
Low pressure
High pressure
EEV steps
Compressor current
Compressor frequency
Condensation temperature
Evaporation temperature
IPM temperature
Displayed in《hydraulic circuit》
DHW tank temperature
Water outlet temperature
Water inlet temperature
Solar tank temperature or DHW pipe temperature