DC INVERTER MULTIFUNCTIONAL
AIR TO WATER HEAT PUMP
User Manual
Model: KING HEAT 6 / 9 / 12 / 18
- 1-

Advertisement

Table of Contents
loading

Summary of Contents for LAMINOX KING HEAT 6

  • Page 1 DC INVERTER MULTIFUNCTIONAL AIR TO WATER HEAT PUMP User Manual Model: KING HEAT 6 / 9 / 12 / 18 - 1-...
  • Page 2: Table Of Contents

    Contents list 1 GENERAL ................................3 2 Safety warnings ..............................3 2.1 Usage and installation warnings ....................... 3 2.2 Personal safety warnings ........................... 4 2.3 Transport, storage and handling warnings ....................5 2.4 Freeze protection warnings........................5 3 SYSTEM DESCRIPTION ............................6 4 INSTALLATION ...............................
  • Page 3: General

    1 GENERAL Thank you for choosing a King Heat heat pump. This is a heat pump capable of providing the ideal level of comfort for your home, always with a suitable hydraulic installation. The unit is an air source heat pump for space heating/cooling and sanitary water heater for houses, apartment blocks and small industrial premises.
  • Page 4: Personal Safety Warnings

    designed. Any other use is considered unsuitable and therefore hazardous. The manufacturer shall not be considered liable under any circumstances for damage caused by unsuitable, erroneous or irrational use. Remove all the packaging and check the contents are complete. In case of doubt, do not use the heat pump.
  • Page 5: Transport, Storage And Handling Warnings

    2.3 Transport, storage and handling warnings The heat pump must be transported, handled and stored vertically. Tipping the machine may cause the compressor or other components damage. Do not twist, loosen or pull the external electric cables of the heat pump. Do not insert any sharp objects through the fan grille or into the fan itself.
  • Page 6: System Description

    and on alert, the heat pump must be connected to the mains and have a power supply, even if it is switched off or not in use. A water filter should be installed in the installation, in order to avoid obstructions in the water circuit of the heat pump.
  • Page 7: Installation

    4 INSTALLATION 4.1 General points for installation engineer Preparation before installation 4.1-1 Make sure the site is large enough to hold all the equipment and has enough operation space. Measure the hoisting path to ensure that the path to the installation site is unobstructed and prevent the equipment from reaching the site during Installation.
  • Page 8: Location Requirements Between Machine And Building

    The receiving surface of the device must: - Allow a solid fixation (Preferably concrete). - Fully support its weight. - Have a permeable area below the condensate drainage hole (earth, gravel bed, sand, etc). - Do not transmit any vibration to the home, recommending the installation of the anti-vibration dampers supplied with the heat pump.
  • Page 9 Consult with the user before choosing the location of the device. It should not be placed next to sensitive walls, such as on the wall next to a bedroom. Make sure that the location of the heat pump is not disruptive to neighbors (sound level, air currents generated, low temperature of the air blown with risk of freezing plants in the path, etc.).
  • Page 10: Condensate Drainage

    The device must be sufficiently accessible for subsequent installation and maintenance work. Make sure that the passage of the hydraulic and electrical connections to the interior of the house is possible and comfortable. The spacing measures indicated in the figure above are those strictly necessary to ensure correct operation of the device;...
  • Page 11: Accessories Supplied

    Preferably install the device in a well-drained place. To do this, it is advisable to provide a bed of gravel, sand or similar materials below said hole. If the drain hole of the heat pump is covered by a mounting base or by the floor, lift the unit to leave a free space of at least 100mm below it.
  • Page 12: Controller

    Drain valve: It is supplied inside the machine, tied with a flange to one leg of the compressor. This key must be installed in the drain socket on the back of the heat pump before filling the water in the heating/cooling circuit.
  • Page 13 A) 6/9/12/18 Space Heating/Cooling + DHW B) 6/9/12/18 Space Heating/Cooling Mode Only C) 2x6/9/12/18 Installation. Space Heating/Cooling + DHW - 13-...
  • Page 14 D)3X6/9/12/18 Installation. Space Heating/Cooling + DHW - 14-...
  • Page 15 Solar Application 1 Solar Application 2 - 15-...
  • Page 16: Pipe Connection

    4.3 Pipe Connection Schematic diagram of water pipe connection between heat pump and buffer tank. For the pipe size is: diameter 28mm, 1 inch, and pipe joint specification. is DN25, material can be copper or stainless steel. The pipe must be flushed before the heat pump is connected, so that any contaminants do not damage the components parts.
  • Page 17: Electrical Connection

    Air vent valves and suitable devices should be fitted for the correct removal of air from the circuit during the filling stage. All water circuit piping MUST be insulated to prevent condensation during operation in cooling mode and reduction of the cooling and heating capacity, as well as to prevent freezing of outside pipes during winter.
  • Page 18: System Diagram

    4.4.1 System Diagram A) P90=1,P65=1 B)P90=0,P65=0 - 18-...
  • Page 19: Wiring Diagram

    4.4.2 Wiring Diagram KING HEAT 6/9/12 - 19-...
  • Page 20 KING HEAT 18 - 20-...
  • Page 21: Installation Drawing

    4.4.3 Auxiliary electrical heater connection 4.4.4 Installation Drawing Connection the main power supply The heat pump is prepared for connection to 230V~ 50Hz in the terminals indicated in the figure (see “wiring Diagram”). Inside the machine, open the front door, and access to the electronic boards area to find the power supply terminals.
  • Page 22: Dhw Anti-Freeze

    The dimension and type of the main supply cables must at all times comply with the rules and regulation in force. Nevertheless, the following table details some recommended features and dimensions, as a guide: Only heat pump Include E1 Include E1 and E2 Power Units Max.
  • Page 23: Ac Anti-Freeze

    withdraw DHW antifreeze. If the water pump starts over 30 minutes, withdraw DHW antifreeze. 4.4.6 AC anti-freeze If the heating supply or return temperature of the heat pump falls below value of parameter P25, heating frost protection will be activated. Depending on the outside air temperature, one of the following actions will be started: •...
  • Page 24: Inspection Before Start Up

    4.5.2 Inspection before Start up 1) Mechanical Inspection: a. Check the cabinet and inside pipe system for possible damage during transportation. b. Check that the heating water circuit is filled and well vented. Check the pipe system for leaks. c. Check the Fan making sure it can move freely. 2) Electric System Inspection a.
  • Page 25 • When the heat pump switches off, the water circulation pump shuts down 60 seconds after the compressor. The fan switches off 15 seconds after the compressor • During defrost, the water circulation pump does not stop running; c) 2 heat source starting When parameter P81= 0, E2 is AC heating control port, When parameter P81=1, E2 is 2nd heat source control port.
  • Page 26: Operating Mode Principle

    Outlet water temperature (C08) ≥ A/C heating set temperature [P02]; If any of the above conditions is met, the electric heater E2 will be turned off. Remarks: During A/C Heating mode, the electric heater E2 is turned on at the beginning of defrosting and the electric heater E2 is turned off at the end of defrost.
  • Page 27: Wired Controller

    5.3 Wired controller 5.3.1 Main interface 5.3.2 Buttons definition and action Note: For the icon “Ts”, only when heat pump is with room temperature sensor, then it is workable. Room temperature sensor is optional. 5.3.2-1 Turn on / off Press ON/OFF button for 3 seconds, can switch the heat pump ON or OFF.
  • Page 28 Click language button , can select language. 5.3.2-3 Time and date setting Click time and date button , can set time and date. 5.3.2-4 Change operating mode Click mode button , can select operating modes. The heat pump will be able to manage up to 5 different modes. (1) Cooling only;...
  • Page 29 A. Auto temp. mode valid or not is up to parameter P18. If the data is set 0, means invalid, 1 means valid. B. Auto heat curve shifting is decided by parameter P09, positive value means move up, negative value means move down. (-10°C ~10°C). C.
  • Page 30 Note: Parameters are not suggested to be modified to avoid taking failure to heat pump. If necessary, please contact professional technician to operate the modification. Please refer to below parameter list for parameters set. Default Default Default Default Name Range (6KW) (9KW) (12KW)
  • Page 31 -8~5 ℃ Coil temperature to active defrost 5~30 ℃ Coil temperature to stop defrost The max defrost time 2~20min 0-no 1-Checking table 2-manual 3- EEV control mode suction superheat 4-Discharge superheat EEV manually initial open steps (heating) 50~480(Only valid when P32=2) EEV manually initial open steps (cooling) 50~480(Only valid when P32=2) In DHW mode, highest water temperature for...
  • Page 32 EVI EEV manually initial open steps(cooling) 40~480 -5~10 ℃ EVI Target superheat (heating) -5~10 ℃ EVI Target superheat (cooling) WIFI data upload interval 30~9999 S Reserved 0-10 ( display value multiply 0.1) 0-Auxiliary electrical heater; 1-second E2 function definition heating source Starting air temp for second heat source(ambient -30~20°C temperature ≤-15 ℃,...
  • Page 33 5.3.2-7 Working status checking Click mode button , and select button <working status and error>, can check “Refrigerant circuit” and “Hydraulic circuit” to know the performance data and working status. Refrigerant circuit Hydraulic circuit 5.3.2-8 System protection and error list checking in the main menu or button in “hydraulic circuit”...
  • Page 34 Coil temp sensor error Coil temperature sensor open circuit or short circuit Suction temp sensor error Suction temp sensor open circuit or short circuit EVI inlet temp sensor error EVI inlet temp sensor open circuit or short circuit EVI outlet temp sensor error EVI outlet temp sensor open circuit or short circuit Discharge temp sensor error Discharge temp sensor open circuit or short circuit...
  • Page 35: Night Mode

    E51-57 ambient temperature <【 P82 】 Ambient temperature exceeds lower limit E59-98 Reserved Inverter model communication failure Main board and inverter board Communication error 5.4 Night mode (1) Night mode valid or not is up to parameter P17. If the data is set 0, means off, 1 means on.
  • Page 36: Technical Specification

    6 TECHNICAL SPECIFICATION 6.1 Internal View KING HEAT 6/9 Top cover Evaporator Electrical box Back side panel Right side support Expansion vessel Electrical box support Compressor Heat exchanger Water pump Base plate Right side service plate Heat exchanger support Front service plate...
  • Page 37 KING HEAT 12 Top cover Evaporator Electrical box Back panel Right side support Expansion vessel Electrical box support Compressor Gas-liquid separator Water pump Heat exchanger Base plate Right side service plate Heat exchanger support Front service plate Front panel Fan grille Mid-support plate Fan blade Fan motor...
  • Page 38 KING HEAT 18 Top cover Evaporator Electrical box Back panel Right side support Expansion vessel Electrical box support Compressor Gas-liquid separator Water pump Base plate Right side service plate Heat exchanger Heat exchanger support Front service plate Front panel Fan grille Mid-support plate Fan blade Fan motor...
  • Page 39: System Drawing

    6.2 System Drawing - 39-...
  • Page 40: Dimensions(Mm)

    6.3 Dimensions(mm) KING HEAT 6/9 /12/18 - 40-...
  • Page 41: Specification

    6.4 Specification King Heat King Heat King Heat King Heat Model: 6DC-32 9DC-32 12DC-32 18DC-32 Heating Capacity Range 2~10 4~13 6~19 Rated Heating Capacity 9.14 12.2 18.50 Rated Heating Input 1.34 2.04 2.73 Rated Heating Current 5.83 8.87 11.87 17.39 4.78 4.49 4.47...
  • Page 42: Maintenance

    7 MAINTENANCE 7.1 Maintenance and Cleaning for User It is good practice to inspect your heat pump regularly. Maintenance should be carried out at least annually to maintain a good lifespan of your heat pump. - Regularly clean the Y type filters every 6 months to ensure that the system is clean and to avoid blockage to the system.
  • Page 43: How To Get The Most Out Of Your Heat Pump

    8 HOW TO GET THE MOST OUT OF YOUR HEAT PUMP It is important to understand that you should operate heat pumps differently to conventional heating systems such as gas boilers. Below are some points you should be aware of: •...
  • Page 44: Appendix I: Wifi Operation

    Appendix I: WIFI operation 1. APP download Please go to APP store or Google market and search “Comfort_life”, download and install the APP, then start it. 2. Register If you are new user, you will need registering: Register→Input your mobile phone number→Get verification code→Input the verification code→Set the password→Complete.
  • Page 45 3. Add device Step 1: Activate the pairing mode on your heat pump controller according to the following: click for 3 seconds to enter following page. Click «Smart mode» to activate WiFi. The symbol will flash quickly. Note: The blinking will stop when the APP is connected to WiFi. Step 2: Now activate the pairing.
  • Page 46 Step 3: If the pairing was successful, you can rename your heat pump per below pictures. Note: Operating factory default in the controller can remove device from APP remotely: turning off the heat pump, and change parameter P87=1 (factory default) in the controller. 4.
  • Page 47 Create a schedule, choose the time, day(s) of the week(s), and the action (turn on or off) and save. 2) Choice of operating modes You can choose between DHW, Heating, Cooling, Heating + DHW, Cooling + DHW modes. - 47-...