E02
Coil temp sensor error
E03
Suction temp sensor error
E04
EVI inlet temp sensor error
E05
EVI outlet temp sensor error
E06
Discharge temp sensor error
E07
DHW temp sensor error
E08
Outlet temp sensor error
E09
Inlet temp sensor error
E10
Liquid refrigerant temp sensor error
E11
High pressure sensor error
E12
Low pressure sensor error
E13
High pressure protection
E14
Low pressure protection
E15
Water flow error
E16
Communication error
E17
Discharge temp too high protection
E18-19
Reserved
E20
IPM abnormal protect
E21
Reserved
E22
Water temp differential too big
E23
DHW anti-freeze twice
E24
AC anti-freeze twice
E25
Reserved
E26
T6 temp sensor error
E27
Ambient temperature exceeds upper limit
E28
Inlet water temp. too high (Cooling)
E29
Room temp sensor error
E30-31
Reserved
E32
Outlet water temp. too high (heating)
E33-35
Reserved
E36
DC fan board communication failure
E37-39
Reserved
E40
Outlet water temp. too low (cooling)
E41-43
Reserved
E44
1# DC motor error
E45
2# DC motor error
E46-49
Reserved
E50
Coil high temp protection
Coil temperature sensor open circuit or short circuit
Suction temp sensor open circuit or short circuit
EVI inlet temp sensor open circuit or short circuit
EVI outlet temp sensor open circuit or short circuit
Discharge temp sensor open circuit or short circuit
DHW temp sensor open circuit or short circuit
Outlet temp sensor open circuit or short circuit
Inlet temp sensor open circuit or short circuit
Sensor open circuit or short circuit
1.sensor fault 2.open circuit or short circuit 3. PCB fault
1.sensor fault 2.open circuit or short circuit 3. PCB fault
1.refrigerant volume too much 2.throttling part error, 3.pressure
sensor error
1.refrigerant volume too little 2.throttling part error, 3 pressure
sensor error
1.Water flow volume too small 2. Water flow switch error
Main board and controller communication error
1.refrigerant volume too little. 2.throttling part error
See Appendix C for detailed code
Check water pump and water pipe filter
The antifreeze function in DHW mode has been activated twice
in 60 minutes
The antifreeze function in A/C mode has been activated twice in
90 minutes
T6 temp sensor open circuit or short circuit
ambient temperature > 45 ℃
cooling: inlet water temp > 40 ℃ , Use with caution or turn off.
temp sensor open circuit or short circuit
Outlet temp > 75 ℃ . Check water pump and water pipe filter
Check communication wire
Outlet temp < 5 ℃ . Check water pump and water pipe filter
Check motor wire or Motor fault
Check motor wire or Motor fault
1.refrigerant volume too much, 2.throttling part error,3.Coil temp
sensor error.
- 34-