Programming The Tracer ® Adaptiview - Trane Tracer AdaptiView Installation Instructions Manual

Rtac rotary chiller display upgrade kit
Hide thumbs Also See for Tracer AdaptiView:
Table of Contents

Advertisement

Installation
Programming the Tracer
1. Configure the UC800 using Tracer
KestrelView report and write all the programming
entries in the order listed.
Note: For more information regarding the use of the
Tracer TU service tool, installation, operation
and programming of the Tracer UC800
controller, operation of the control system, and
a guide to the diagnostics and troubleshooting
of the control system, please refer to the
following manuals:
• TTU-SVN01*-EN (Getting Started Guide: Tracer
TU Service Tool)
• RTAC-SVX01*-EN (Installation, Operation, and
Maintenance, Series R Air-Cooled Helical Rotary
Liquid Chillers)
NOTICE:
Separate AC Power Required for
Computers when Working on Tracer
AdaptiView!
Failure to follow instructions below could result in
damage to the controller. When doing any service work
on a Tracer AdaptiView control system that requires
connecting a laptop computer running Tracer TU
service tool software to the UC800 controller, the
laptop must be operated from a SEPARATE AC power
source AT ALL TIMES. NEVER run the laptop on internal
battery power alone while connected to a UC800
controller! Should the computer's internal battery die
or malfunction while connected to a UC800, fatal
corruptions could occur to the electronic files within
the controller that will render it completely inoperable
and unable to accept new programming, requiring it to
be replaced with new UC800. Damaging a UC800
controller in this manner is not covered under any
warranty!
2. Obtain a working AC power adapter with which to
power the technician's laptop.
Table 15. Mapping table
Compressor
Manufacturing
(a)
Frame Size
Location
K1
Charmes
K1
Charmes
K2
Charmes
K2
Charmes
L1
Charmes
L1
Charmes
L2
Charmes
L2
Charmes
M1,M3
Curitiba, Pueblo, Taicang
M1,M3
Curitiba, Pueblo, Taicang
20
®
AdaptiView™
®
TU. Refer to the
Unit Type
(b)
(Model Number Digit 12)
N = Standard, A = Extra Efficiency
H = High Efficiency
N = Standard, A = Extra Efficiency
H = High Efficiency
N = Standard, A = Extra Efficiency
H = High Efficiency
N = Standard, A = Extra Efficiency
H = High Efficiency
H = High Efficiency
N = Standard, A = Extra Efficiency
3. Connect the computer with the Tracer TU service tool
software to the service port of the Tracer UC800
controller with a USB type A/B cable.
4. Open Tracer TU.
Note: The UC800 ships with no software loaded.
When first connecting to Tracer TU, a pop-up
will direct you toward the software download
page.
5. Select the appropriate product type (RTAC), and select
the latest version listed.
6. Click the Upgrade Device button when complete. See
Figure
29.
Figure 29. Application software download
7. Use the Chiller Report PDF to manually copy the
configuration parameters in Tracer
for correct mappings. After the configuration is saved,
Tracer TU will automatically proceed to LLID Binding
view. Check to see if any of the listed devices need to
be bound, indicated by a red box. See
Unit
(c)
Voltage
400
400
400
400
400
400
400
400
575
575
®
TU. See
Table 15
Figure 30, p.
Compressor
CT Meter
(d)
(e)
RLA
Scale
51
75
51
75
61
75
61
75
75
100
75
100
92
100
92
100
90
100
94
100
RCDA-SVN002C-EN
23.
(f)

Advertisement

Table of Contents
loading

Table of Contents