Restore System Power

To prevent an unexpected chiller start up when system
power is first restored, implement the appropriate
preventative measure from the following list:
1. If the chiller is equipped with an external Auto Stop
button, disconnect the wire from terminal J2-1 on the
1U4 LLID.
2. If the chiller is not equipped with an external Auto Stop
button, disconnect the factory installed jumper wire
end from terminal J2-1 on the 1U4 LLID. See
p.
19.
Figure 28. Prevent unexpected chiller start-up before
restoring power
3. Perform a final inspection of the control panel
enclosure before restoring system power
a. Remove any tools and use a shop vacuum to
remove any dirt or debris that may have been
created during the installation process.
b. Confirm that all upgrade kit wiring has been
correctly routed and that all terminal connections
have been properly made.
c. Inspect the rest of the electrical wiring and
components within the enclosure to ensure that no
wiring connections were accidently loosened or
disconnected during the kit installation process.
d. Reinstall all panels.
4. Remove all lockout/tagout devices used at the power
supply panels for the chiller equipment.
5. Warn all personnel in the area that system power is
about to be restored.
6.
Energize the system according to all applicable
standard safety procedures
RCDA-SVN002C-EN