Advertisement

5 Connecting to power supply

Note safety instructions
Take note of safety
instructions for Ex
applications
Voltage supply
Connection cable
Cable gland ½ NPT
Cable screening and
grounding
22
5
Connecting to power supply
5.1

Preparing the connection

Always keep in mind the following safety instructions:
Connect only in the complete absence of line voltage
If voltage surges are expected, overvoltage arresters should be
installed according to Profibus specifications
In hazardous areas you must take note of the respective regulations,
conformity and type approval certificates of the sensors and power
supply units.
Power supply is provided by a Profibus DP/PA segment coupler. The
power supply range can differ depending on the instrument version.
The data for power supply are specified in chapter " Technical data".
Connection is made with shielded cable according to the Profibus
specification. Power supply and digital bus signal are carried over the
same two-wire connection cable.
Make sure that the cable used has the required temperature resist-
ance and fire safety for max. occurring ambient temperature
Use cable with round cross-section. A cable outer diameter of
5 ... 9 mm (0.2 ... 0.35 in) ensures the seal effect of the cable gland.
If you are using cable with a different diameter or cross-section,
exchange the seal or use a suitable cable gland.
Please make sure that your installation is carried out according to the
Profibus specification. In particular, make sure that the termination of
the bus is done with appropriate terminating resistors.
On the instrument with cable entry ½ NPT and plastic housing there is
a metallic ½" threaded insert moulded into the plastic housing.
Caution:
No grease should be used when screwing the NPT cable gland or
steel tube into the threaded insert. Standard grease can contain
additives that corrode the connection between threaded insert and
housing. This would influence the stability of the connection and the
tightness of the housing.
In systems with potential equalisation, connect the cable screening
directly to ground potential at the power supply unit, in the connection
box and at the sensor. The screen in the sensor must be connected
directly to the internal ground terminal. The ground terminal outside
on the housing must be connected to the potential equalisation (low
impedance).
In systems without potential equalisation, connect the cable screen-
ing directly to ground potential at the power supply unit and at the
sensor. In the connection box or T-distributor, the screening of the
short stub to the sensor must not be connected to ground potential
or to another cable screening. The cable screenining to the power
VEGASON 61 • Profibus PA