SV2 Series Safety Shut-off Valves
• For detailed C6097 installation instructions when used with the SV2 Series valves, refer to the SV2 Series valves
installation instructions, document 32-00018.
• You may want to mount the C6097 on the same side as the valve electrical enclosure for easy access when the valve is
mounted in the valve train.
• If you need to replace a pressure access location cover, the tightening torque should be between 1.36 to 1.81 Nm
(12 to 16 in-lbf).
• If you need to replace a pressure access port plug, the tightening torque should be 6-8 Nm (53-71 in-lbf).
WARNING!
Explosion Hazard and Electrical Shock Hazard.
Can cause explosion, serious injury or death.
• Turn off gas supply before starting installation
• Disconnect power supplies before beginning installation
• More than one disconnect can be involved
52
32-00029—02