SV2 SERIES SAFETY SHUT-OFF VALVES USER MANUAL
The cloning screens may be accessed one of two ways (refer to
Fig.
67):
• Selecting the icon of a connected valve and selecting the 'Valve Production Cloning' button from the pop-up screen
• Selecting the 'Valve Production Cloning' button in the Setup & Tests menu for a connected valve
Fig. 67: Valve Production cloning selection.
The cloning feature allows the Installer or OEM user to load a previously saved fuel/air valve configuration to use for another
application or as a basis for making another configuration. Note that there are few a limitations to the cloning procedure:
• The cloned fuel/air valve configuration only contains the OEM Setup and Ignition Setup parameters and Base Curve.
• The fuel/air Correction Curve and the recorded pre-ignition air values as well as the LGP/HGP and POC settings are not part
of the cloned configuration because they are related to the valve with which they were created.
After the configuration is uploaded to the valve, the safety parameter verification procedure will need to be completed.
When all questions and confirmations are completed, you will be directed to press the valve reset button within 30 seconds. This
final step is required to make the valve operational. Once complete, the screen will show 'All safety parameters are OK'.
NOTE: If the valve is powered during the safety verification procedure, it will not be un-powered, unless a fault occurs.
After cloning is complete, start the valve in the Installer or OEM mode and set the new fuel/air Correction Curve and record the
Ign. Air Level to make the valve fully operational.