3.6

UNPACKING

The UPS and Battery Cabinets may be shipped packaged in wooden crates.
Move the cabinets as close as possible to the final location before removing from the pallet.
Remove the cabinet from the wooden crates with care, because of the heavy weight of the equipment.
White color
Red color
Fig. 3.6-1 ShockWatch device
Fig. 3.6-2 TiltWatch device
NOTE !
Take care not to damage the UPS when moving by forklift.
A damaged UPS must never be installed or connected to Utility or Battery!
In case of any damage sustained during the transport, immediately inform the
shipping agent!
A detailed report of the damage is necessary for any indemnity claim.
For parallel systems, the delivery also includes the bus control cables for inter-
connecting the UPS modules.
Packing material recycling
GE, in compliance with environment protection, use only environmentally friendly
material.
UPS packing materials must be recycled in compliance with all applicable
regulations.
Modifications reserved
OPM_SGS_ISG_M75_M75_2US_V010.doc
=
without any anomaly
=
anomaly evidence
The package of the SG Series 750 &
SG Series 750 T12 is equipped with
ShockWatch (indicator for shock),
and
TiltWatch
(indicator
overthrow) on the outside.
These devices indicate an eventual
shock or overthrow during transport.
Whenever these devices show a
possible anomaly, the UPS shall not
be commissioned before consulting
a "Service Center".
Installation Guide SG Series 750 UL S2 & SG Series 750 T12 UL S2
for
Page 19/49