MAINTENANCE TIME

Part description
ELECTRODES
FLAME DISC
IONISATION PROBE
COMBUSTION HEAD
COMPONENTS
INSULATING GASKET
GAS DELIVERY COUPLING SEAL
AIR GRILLE/DAMPERS
AIR DAMPER BEARINGS
FAN
AIR PRESSURE SWITCH
AIR PRESSURE PORT AND PIPES
FLAME SENSOR
GAS PRESSURE SWITCH
ELECTRIC MOTORS
MECHANICAL CAM
LEVERS/TIE-RODS/BALL JOINTS
ELECTRICAL SYSTEM
INVERTER
CO PROBE
O2 PROBE
COMBUSTION HEAD EXTRACTION
KIT
GAS FILTER
HYDRAULIC/GAS SEALS
CO CONTROL
CO2 CONTROL
BACHARACH SMOKE INDEX
CONTROL
NOX CONTROL
IONISATION CURRENT CONTROL
SMOKE TEMPERATURE CONTROL
GAS PRESSURE REGULATOR
IMPORTANT
In case of heavy-duty operation or when using special fuels, the maintenance intervals must be reduced adapting them to the real
operating conditions, according to the indications of the maintenance technician.
COMBUSTION HEAD
VISUAL INSPECTION OF THE INTEGRITY OF CERAMICS. TIP GRINDING, CHECK DISTANCE, CHECK
ELECTRICAL CONNECTION
INTEGRITY VISUAL CHECK FOR ANY DEFORMATIONS, CLEANING,
VISUAL INSPECTION OF THE INTEGRITY OF CERAMICS. TIP GRINDING, CHECK DISTANCE, CHECK
ELECTRICAL CONNECTION
INTEGRITY VISUAL CHECK FOR ANY DEFORMATIONS, CLEANING,
SEAL VISUAL INSPECTION AND POSSIBLE REPLACEMENT
SEAL VISUAL INSPECTION AND POSSIBLE REPLACEMENT
AIR LINE
GREASING, (Note: apply only on burners with bearings requiring lubrication)
FAN AND SCROLL CLEANING, DRIVE SHAFT GREASING
SAFETY COMPONENTS
VARIOUS COMPONENTS
COOLING FAN CLEANING, BEARING NOISE CHECK
CHECK OF WEAR AND OPERATION, GREASING OF SLIDING BLOCK AND SCREWS
CHECK OF ANY WEAR, COMPONENT LUBRICATION
CHECK OF CONNECTIONS AND TERMINAL TIGHTENING
COOLING FAN CLEANING AND TERMINAL TIGHTENING
CLEANING AND CALIBRATION
CLEANING AND CALIBRATION
CHECKING WEAR AND OPERATION
FUEL LINE
REPLACING THE FILTERING ELEMENT
CHECK OF ANY LEAKAGES
COMBUSTION PARAMETERS
COMPARISON WITH VALUES RECORDED AT SYSTEM START-UP
COMPARISON WITH VALUES RECORDED AT SYSTEM START-UP
COMPARISON WITH VALUES RECORDED AT SYSTEM START-UP
COMPARISON WITH VALUES RECORDED AT SYSTEM START-UP
COMPARISON WITH VALUES RECORDED AT SYSTEM START-UP
COMPARISON WITH VALUES RECORDED AT SYSTEM START-UP
PRESSURE MEASURED AT START-UP
25 / 30
0006080749_202206
Action to be performed
CLEANING
CLEANING
CLEANING
CLEANING
FUNCTIONAL INSPECTION
ENGLISH
Gas
YEAR
YEAR
YEAR
YEAR
YEAR
YEAR
YEAR
YEAR
YEAR
YEAR
YEAR
YEAR
YEAR
YEAR
YEAR
YEAR
YEAR
YEAR
YEAR
YEAR
YEAR
YEAR
YEAR
YEAR
YEAR
n.a.
YEAR
YEAR
YEAR
YEAR

Advertisement