When one Passport 15000 or 20000 is shipped in the NEBS 2000 frame, the
insulation boots and lugs are provided for the second set of BIMs. This
accommodates adding a second switch of the same kind to the frame. The
equipment package NTQS10 or NTQH10 includes the wiring harnesses for
adding a second shelf.
Location of the BIMs
The breaker interface modules (BIMs) are located in the breaker interface
panel (BIP). In four-BIM models, all BIM slots are filled up to the alarm
module. In two-BIM models, the BIMs are located in the two right-hand slots
next to the alarm module, with the two left BIM slots covered with filler
plates. See the figure "The BIP in a NEBS 2000 frame, front view" (page 52).
See "BIM filler plates" (page 62).
Functions of the BIMs
The power breakers on each BIM control the -48/-60 V dc A and B power
supplies to the power interface modules (PIMs) and to the upper and lower
cooling units. See the figure "The BIP in a NEBS 2000 frame, front view"
(page 52) for the location of the power breakers.
For a Passport 15000, each BIM with PEC NT6C60PA supports a maximum
of five PCB-mount circuit breakers made up of four 20-amp shelf breakers
and one central 5-amp cooling unit breaker. See the table "Circuit breaker
configuration for each BIM of a Passport 15000 or 20000" (page 55). The
position of the breaker is relative to facing the front of the BIP.
Table 1
Circuit breaker configuration for each BIM of a Passport 15000 or 20000
Location of
circuit breaker
Passport 15000 20 amp
Passport 20000 25 amp
Chapter 2 Breaker interface panel 55
Left
Middle
left
20 amp
25 amp
shelf
shelf
upper half
upper half
Passport 15000, 20000 Hardware Description
Middle
Middle
right
5 amp
20 amp
5 amp
25 amp
cooling
shelf
units
lower half
Right
20 amp
25 amp
shelf
lower half
5.2S2