Download Print this page

Ecoflam MAX 4 Manual page 15

Light oil burners
Hide thumbs Also See for MAX 4:

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 7
Start up
- Setting data table - Air regulation
NOZZLE
gph
spry
0,50
60°S
0,60
60°S
0,65
60°S
0,75
60°S
0,85
60°S
1,00
60°S
1,00
60°S
1,10
60°S
1,25
60°S
1,35
60°S
1,50
60°S
1,65
60°S
1,75
60°S
1,50
60°S
1,65
60°S
1,75
60°S
2,00
60°S
2,25
60°S
2,50
60°S
2,75
60°S
The settings above are basic settings.
These adjustment values are normally
suitable for commissioning the burner.
These values have been determined in
our test labs and are useful for the first
A
B
MAX 4-8-12
420010029304
PUMP
OUTPUT
bar
kg/h
12
2
12
2,4
12
2,7
10
2,94
12
3,5
12
4,35
12
4,35
12
4,5
12
5
12
5,6
10
5,8
12
7
12
7,6
12
6,2
12
7
12
7,6
12
8,3
12
9,3
12
10,4
12
11,5
switch-on as final setting must be done
using a combustion analyzer.
Favourable combustion values can be
achieved using the following nozzles:
A1
MAX 8-12
!
Risk of air blast!
Continuously check CO, CO 2 and soot emissions when adjusting the output of
the burner. Optimise combustion values in the event of CO formation. CO must
not exceed 50 ppm.
FIRING HEAD SETTING
Pos.
0
0,5
0,5
1
3
4
1
1
2
2,5
1
4
4,5
0
1
2
3
3,5
4
4,5
MAX 4
B
+
-
AIR DAMPER SETTING
Pos.
3
4
5
4
8
10
4
5,5
6,2
7,3
4
9,2
10,5
2
3,5
5
7
8,5
9,5
10,5
DANFOSS H÷S 80°÷60°
DELAVAN W 60°
STEINEN S 60°
Air damper setting (A).
To act on the screw in figure:
• to increase output, turn screwdriver
clockwise
• to reduce output, turn screwdriver
counterclockwise
Air damper setting (A1).
To adjust air flow , loosen the two screw B
and turn the air damper as required.
Tighten the screw B.
Firing head setting (B).
To act on the screw in figure:
• turn Allen key till you reach the
requested value (index 0-4,5).
www.ecoflam-burners.com
EN
15

Advertisement

loading

This manual is also suitable for:

Max 8Max 12