Page 1
Esquemas eléctrico e hidráulico Электрические и гидравлические схемы Spare parts list Pièces de rechange Parti ricambi Запчасти Piezas de recambio 3142729 MAX 15 TC 3142730 MAX 15 TL 3142731 MAX 20 TC 3142732 MAX 20 TL 3142733 MAX 30 TC...
An eventual obstraction could damage the pump sealing device. ONE PIPE SYSTEM: If the oil supply One-pipe system circuit is one-pipe system, the pump needs to be modified following intructions in the picture. DANFOSS SUNTEC www.ecoflam-burners.com 420010371901...
Page 8
A as specified in the boiler manufacturer’s instructions must be observed. Exhaust system To avoid unfavourable noise emissions, right-angled connectors should not be used on the flue gas side of the boiler. 420010371901 www.ecoflam-burners.com...
Page 9
• The heat request must be available. • All electrical connections must be correct. • Fuel tanks must be full. • The heat generator and heating system • The fuel supply lines must be www.ecoflam-burners.com 420010371901...
Page 10
Two-pipe siphon feed system FEEDING LINE WITH DANFOSS BFP21 R3 Length pipe (m) H = x-y ø 6 mm ø 8 mm ø 10 mm Two-pipe lift system Length pipe (m) ø 6 mm ø 8 mm ø 10 mm 420010371901 www.ecoflam-burners.com...
• to increase output, turn screwdriver counterclockwise. • to reduce output, turn screwdriver clockwise. Note: screw B not used. Firing head setting (B). To act on the screw in figure: • turn Allen key till you reach the requested value (index 0-5). www.ecoflam-burners.com 420010371901...
Page 12
- Starting attempt with flame monitor unlit: malfunction after the restart and end of the automatic combustion control unit the safety time must switch to malfunction at the end of the safety time 420010371901 www.ecoflam-burners.com...
Fit the new nozzle by the same care. Note: Always check the position of electrodes after having replaced the nozzle (see illustration). A wrong position could cause ignition troubles. www.ecoflam-burners.com 420010371901...
Check ignition circuit, electrode adjustment. Clean/replace electrodes. Clean/replace flame monitor. Replace the following items as required: Flame extinguishing Flame goes out during Ignition electrodes/ignition cables/ignition during operation operating phase transformer/nozzle/pump/solenoid valve/ automatic combustion control unit. 420010371901 www.ecoflam-burners.com...