Indicates a situation that could result in equipment or property damage. INFORMATION Indicates useful tips or additional information. Symbols used on the unit: ARXM50~71+RXM42~71N2V1B(9) + RXP50~71M2V1B + Installer reference guide RXA42+50+RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-7H – 2019.12...
Improper installation or attachment of equipment or accessories could result in electric shock, short-circuit, leaks, fire or other damage to the equipment. Only use accessories, optional equipment and spare parts made or approved by Daikin. WARNING Make sure installation, testing and applied materials comply with applicable legislation (on top of the instructions described in the Daikin documentation).
Do NOT use means to accelerate the defrosting process or to clean the equipment, other than those recommended by the manufacturer. ▪ Be aware that R32 refrigerant does NOT contain an odour. ARXM50~71+RXM42~71N2V1B(9) + RXP50~71M2V1B + Installer reference guide RXA42+50+RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-7H – 2019.12...
Page 7
Joints made in installation between parts of refrigerant system shall be accessible for maintenance purposes. WARNING Make sure installation, servicing, maintenance and repair comply with instructions from Daikin and with applicable legislation (for example national gas regulation) and are executed only by authorised persons. Installation space requirements NOTICE ▪...
Page 8
Wall-mounted units ≥2.2 m Ceiling-mounted units 3 Use the graph or table to determine the minimum floor area. m (kg) 1.843 7.956 ARXM50~71+RXM42~71N2V1B(9) + RXP50~71M2V1B + Installer reference guide RXA42+50+RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-7H – 2019.12...
Excessive refrigerant concentrations in a closed room can lead to oxygen deficiency. ▪ Toxic gas may be produced if refrigerant gas comes into contact with fire. ARXM50~71+RXM42~71N2V1B(9) + RXP50~71M2V1B + Installer reference guide RXA42+50+RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-7H – 2019.12...
Page 10
A siphon tube is NOT present Charge with the cylinder upside down. ▪ Open refrigerant cylinders slowly. ARXM50~71+RXM42~71N2V1B(9) + RXP50~71M2V1B + Installer reference guide RXA42+50+RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-7H – 2019.12...
Do NOT touch electrical components with wet hands. ▪ Do NOT leave the unit unattended when the service cover is removed. ARXM50~71+RXM42~71N2V1B(9) + RXP50~71M2V1B + Installer reference guide RXA42+50+RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-7H – 2019.12...
Page 12
▪ Over-tightening the terminal screws may break them. ARXM50~71+RXM42~71N2V1B(9) + RXP50~71M2V1B + Installer reference guide RXA42+50+RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-7H – 2019.12...
Page 13
Running the product in reversed phase can break the compressor and other parts. ARXM50~71+RXM42~71N2V1B(9) + RXP50~71M2V1B + Installer reference guide RXA42+50+RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-7H – 2019.12...
The original documentation is written in English. All other languages are translations. Technical engineering data ▪ A subset of the latest technical data is available on the regional Daikin website (publicly accessible). ▪ The full set of latest technical data is available on the Daikin Business Portal (authentication required).
Page 15
What to do in case of problems Disposal How to dispose of the system Technical data Specifications of the system Glossary Definition of terms ARXM50~71+RXM42~71N2V1B(9) + RXP50~71M2V1B + Installer reference guide RXA42+50+RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-7H – 2019.12...
Keep the unit away from rain or damp conditions. At least 2 persons MUST handle the box with the unit. 3.2 Outdoor unit 3.2.1 To unpack the outdoor unit ARXM50~71+RXM42~71N2V1B(9) + RXP50~71M2V1B + Installer reference guide RXA42+50+RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-7H – 2019.12...
When installing or servicing several units at the same time, make sure NOT to switch the service panels between different models. 4.2.1 Identification label: Outdoor unit Location ARXM50~71+RXM42~71N2V1B(9) + RXP50~71M2V1B + Installer reference guide RXA42+50+RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-7H – 2019.12...
The appliance shall be stored in a room without continuously operating ignition sources (example: open flames, an operating gas appliance or an operating electric heater). ARXM50~71+RXM42~71N2V1B(9) + RXP50~71M2V1B + Installer reference guide RXA42+50+RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-7H – 2019.12...
It is recommended to install the outdoor unit with the air inlet facing the wall and NOT directly exposed to the wind. ARXM50~71+RXM42~71N2V1B(9) + RXP50~71M2V1B + Installer reference guide RXA42+50+RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-7H – 2019.12...
Page 22
If the outdoor unit is exposed to direct sea winds, install a windbreaker. ▪ Height of windbreaker≥1.5×height of outdoor unit ▪ Mind the service space requirements when installing the windbreaker. ARXM50~71+RXM42~71N2V1B(9) + RXP50~71M2V1B + Installer reference guide RXA42+50+RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-7H – 2019.12...
20 mm to prevent condensation on the surface of the insulation. ARXM50~71+RXM42~71N2V1B(9) + RXP50~71M2V1B + Installer reference guide RXA42+50+RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-7H – 2019.12...
All components procured on-site and all electrical construction MUST comply with the applicable legislation. WARNING ALWAYS use multicore cable for power supply cables. ARXM50~71+RXM42~71N2V1B(9) + RXP50~71M2V1B + Installer reference guide RXA42+50+RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-7H – 2019.12...
Do NOT leave the unit unattended when the service cover is removed. 6.2.2 To open the outdoor unit DANGER: RISK OF ELECTROCUTION DANGER: RISK OF BURNING 3× ARXM50~71+RXM42~71N2V1B(9) + RXP50~71M2V1B + Installer reference guide RXA42+50+RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-7H – 2019.12...
Fix the unit securely by means of foundation bolts in accordance with the foundation drawing. Prepare 4 sets of M8 or M10 anchor bolts, nuts and washers (field supply). ARXM50~71+RXM42~71N2V1B(9) + RXP50~71M2V1B + Installer reference guide RXA42+50+RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-7H – 2019.12...
1 Prepare 2 cables as indicated in the following illustration (field supply). 2 Place the 2 cables over the outdoor unit. ARXM50~71+RXM42~71N2V1B(9) + RXP50~71M2V1B + Installer reference guide RXA42+50+RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-7H – 2019.12...
To prevent gas leakage, apply refrigeration oil only to the inside of the flare. Use refrigeration oil for R32. ▪ Do NOT reuse joints. ARXM50~71+RXM42~71N2V1B(9) + RXP50~71M2V1B + Installer reference guide RXA42+50+RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-7H – 2019.12...
4 Flare the pipe. Set exactly at the position as shown in the following figure. Flare tool for R32 Conventional flare tool (clutch type) Clutch type Wing nut type (Ridgid-type) (Imperial-type) 0~0.5 mm 1.0~1.5 mm 1.5~2.0 mm ARXM50~71+RXM42~71N2V1B(9) + RXP50~71M2V1B + Installer reference guide RXA42+50+RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-7H – 2019.12...
1 Connect the liquid refrigerant connection from the indoor unit to the liquid stop valve of the outdoor unit. Liquid stop valve ARXM50~71+RXM42~71N2V1B(9) + RXP50~71M2V1B + Installer reference guide RXA42+50+RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-7H – 2019.12...
Make sure that the gas stop valve and liquid stop valve are firmly closed before performing the leak test or vacuum drying. ARXM50~71+RXM42~71N2V1B(9) + RXP50~71M2V1B + Installer reference guide RXA42+50+RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-7H – 2019.12...
2 Leave as is for 4-5 minutes and check the pressure: If the pressure… Then… Does not change There is no moisture in the system. This procedure is finished. ARXM50~71+RXM42~71N2V1B(9) + RXP50~71M2V1B + Installer reference guide RXA42+50+RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-7H – 2019.12...
Typical workflow – Charging additional refrigerant typically consists of the following stages: 1 Determining if and how much you have to charge additionally. 2 If necessary, charging additional refrigerant. ARXM50~71+RXM42~71N2V1B(9) + RXP50~71M2V1B + Installer reference guide RXA42+50+RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-7H – 2019.12...
Do NOT use cleaning materials or means to accelerate the defrosting process other than those recommended by the manufacturer. ▪ Be aware that the refrigerant inside the system is odourless. ARXM50~71+RXM42~71N2V1B(9) + RXP50~71M2V1B + Installer reference guide RXA42+50+RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-7H – 2019.12...
If a complete recharge is necessary, the total refrigerant charge is: the factory refrigerant charge (see unit name plate) + the determined additional amount. ARXM50~71+RXM42~71N2V1B(9) + RXP50~71M2V1B + Installer reference guide RXA42+50+RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-7H – 2019.12...
2 Fix the label on the inside of the outdoor unit near the gas and liquid stop valves. ARXM50~71+RXM42~71N2V1B(9) + RXP50~71M2V1B + Installer reference guide RXA42+50+RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-7H – 2019.12...
Do NOT branch the power supply for the drain pump, etc. from the terminal block. This could result in electrical shock or fire. ARXM50~71+RXM42~71N2V1B(9) + RXP50~71M2V1B + Installer reference guide RXA42+50+RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-7H – 2019.12...
6.8.2 To close the outdoor unit NOTICE When closing the outdoor unit cover, make sure that the tightening torque does NOT exceed 1.3 N•m. ARXM50~71+RXM42~71N2V1B(9) + RXP50~71M2V1B + Installer reference guide RXA42+50+RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-7H – 2019.12...
1 Remove the service cover. 2 Disconnect the selective standby electricity saving connector. 3 Turn on the main power supply. ARXM50~71+RXM42~71N2V1B(9) + RXP50~71M2V1B + Installer reference guide RXA42+50+RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-7H – 2019.12...
The indoor unit is properly mounted. The outdoor unit is properly mounted. The system is properly earthed and the earth terminals are tightened. ARXM50~71+RXM42~71N2V1B(9) + RXP50~71M2V1B + Installer reference guide RXA42+50+RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-7H – 2019.12...
Even if the unit is turned OFF, it consumes electricity. ▪ When the power turns back on after a power break, the previously selected mode will be resumed. ARXM50~71+RXM42~71N2V1B(9) + RXP50~71M2V1B + Installer reference guide RXA42+50+RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-7H – 2019.12...
Commissioning 8.6 Starting up the outdoor unit See the indoor unit installation manual for configuration and commissioning of the system. ARXM50~71+RXM42~71N2V1B(9) + RXP50~71M2V1B + Installer reference guide RXA42+50+RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-7H – 2019.12...
Show the user what to do for the maintenance of the unit. ▪ Explain the user about energy saving tips as described in the operation manual. ARXM50~71+RXM42~71N2V1B(9) + RXP50~71M2V1B + Installer reference guide RXA42+50+RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-7H – 2019.12...
Do NOT rinse the unit. This may cause electric shocks or fire. 10.3 Checklist for yearly maintenance of the outdoor unit Check the following at least once a year: ARXM50~71+RXM42~71N2V1B(9) + RXP50~71M2V1B + Installer reference guide RXA42+50+RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-7H – 2019.12...
Do NOT use the brazing torch. ▪ Use approved refrigerants and lubricants only. DANGER: RISK OF BURNING Do NOT touch the compressor with bare hands. ARXM50~71+RXM42~71N2V1B(9) + RXP50~71M2V1B + Installer reference guide RXA42+50+RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-7H – 2019.12...
11.3.2 Symptom: The unit is NOT heating or cooling as expected Possible causes Corrective action Wrong connection of the electrical Connect the electrical wires correctly. wires ARXM50~71+RXM42~71N2V1B(9) + RXP50~71M2V1B + Installer reference guide RXA42+50+RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-7H – 2019.12...
When the unit is not operating, the LEDs on the PCB are turned off in order to save power. ▪ Even when the LEDs are off, the terminal block and the PCB may be powered. ARXM50~71+RXM42~71N2V1B(9) + RXP50~71M2V1B + Installer reference guide RXA42+50+RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-7H – 2019.12...
4 Check on the manifold if the vacuum is reached. 5 After 2-3 minutes, close the gas stop valve and stop forced cooling. ARXM50~71+RXM42~71N2V1B(9) + RXP50~71M2V1B + Installer reference guide RXA42+50+RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-7H – 2019.12...
If forced cooling is used and the outside temperature is <−10°C, the safety device may prevent operation. Warm the outside temperature thermistor on the outdoor unit to ≥−10°C. Result: Operation will start. ARXM50~71+RXM42~71N2V1B(9) + RXP50~71M2V1B + Installer reference guide RXA42+50+RXF50+60B2V1B + RXF71A2V1B + RXJ50N2V1B + ARXF50~71A2V1B R32 split series 4P513661-7H – 2019.12...
Technical data 13 Technical data ▪ A subset of the latest technical data is available on the regional Daikin website (publicly accessible). ▪ The full set of latest technical data is available on the Daikin Business Portal (authentication required). 13.1 Wiring diagram The wiring diagram is delivered with the unit, located inside of the outdoor unit (bottom side of the top plate).
Optional equipment Equipment made or approved by Daikin that can be combined with the product according to the instructions in the accompanying documentation. Field supply Equipment NOT made by Daikin that can be combined with the product according to the instructions in the accompanying documentation.
Page 68
4P513661-7H 2019.12 Verantwortung für Energie und Umwelt...