Daikin ARKC18RV2S Service Manual page 10

Outdoor unit 4.2/5.0/6.0 kw class 18000/24000 btu/h class

Advertisement

Electrical Box
Step
8
Cut the clamp.
9
Pull out the outdoor
heat exchanger
thermistor.
10 Disconnect the
connector [S40] and
pull out the clamp.
11 Disconnect the
connector [S20] and
remove the clamp.
8
Procedure
[S40]
[S20]
Be careful not to lose the clip
for the thermistor.
Clamp
Outdoor heat
exchanger
thermistor
(R20543)
[S40]: overload protector
Clamp
(R20544)
[S20]: electronic expansion
Clamp
(R20545)
Si001413EB
Points
Clip
(R3264)
valve coil
Removal Procedure