FMU5X, FMU5Z
MULTIFAMILY CEILING MOUNT FAN COIL
NOTE: Read the entire instruction manual before starting the installation.

Table of Contents

SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Refrigerant Charge and Room Area Limitations . . . . . . . . . . . . . . 2
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Check Equipment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Mount Fan Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Supply-Air Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
RETURN AIR. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Condensate Drain. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
TXV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
LEAK DISSIPATION SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Leak Dissipation System Self-Test . . . . . . . . . . . . . . . . . . . . . . . . 8
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
SEQUENCE OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Continuous Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Cooling Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Heat Pump Heating Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Electric Heat Or Emergency Heat Mode . . . . . . . . . . . . . . . . . . . . 9
CARE AND MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
ELECTRICAL WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
DUCTWORK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

SAFETY CONSIDERATIONS

Improper installation, adjustment, alteration, service, maintenance, or
use can cause explosion, fire, electrical shock, or other conditions which
may cause death, personal injury or property damage. Consult a
qualified installer, service agency, or your distributor or branch for
information or assistance. The qualified installer or agency must use
factory-authorized kits or accessories when modifying this product.
Refer to individual instructions packaged with kits or accessories when
installing.
Follow all safety codes. Wear safety glasses, protective clothing, and
work gloves. Use quenching cloth for brazing operations. Have a fire
extinguisher available. Read these instructions thoroughly and follow all
warning or cautions included in literature and attached to the unit.
Consult local building codes and the current editions of the National
Electrical Code (NEC) NFPA 70.
In Canada, refer to the current editions of Canadian Electrical Code CSA
C22.1.
Recognize safety information. This is the safety alert symbol
you see this symbol on the unit and in instructions or manuals, be alert to
the potential for personal injury. Understand the signal words
DANGER, WARNING, and CAUTION. These words are used with the
safety alert symbol. DANGER identifies the most serious hazards which
will result in severe personal injury or death. WARNING signifies
hazards which could result in personal injury or death. CAUTION is
used to identify unsafe practices, which may result in minor personal
injury or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability, or
operation.
Installation Instructions
. When

INTRODUCTION

FMU5X and FMU5Z Fan Coils are designed for horizontal orientation
and are suitable for ceiling installations in conditioned spaces. These
units are available with field -installed electric heat, and are used indoors
as the fan coil for split -system heat pumps or air conditioners. FMU5X
and
FMU5Z
models
all
available in 18,000 through 36,000 Btuh nominal cooling capacities.
FMU5X units utilize a 3-speed PSC motor. FMU5Z units utilize a
5-speed ECM motor.
Field-installed heaters are available in 3, 5, 6, 7.5 and 10 kW sizes. The
coil is equipped with sweat-type connections and is vapor-charged with
dry nitrogen.
Units are designed for horizontal applications only. Local codes may
limit this free-air-return type unit to installation in single-level
applications.
NOTE: Nuisance sweating may occur if the unit is installed in a humid
location with low airflow.
WARNING
!
PROPERTY OR PERSONAL
INJURY HAZARD
Risk of fire. Flammable refrigerant
used.
To be repaired only by trained service personnel. Do
not puncture refrigerant tubing.
Auxiliary devices which may be ignition sources shall not be installed
in the ductwork, other than auxiliary devices listed for use with the
specific appliance. See instructions.
Dispose of refrigerant properly in accordance with federal or local
regulations.
Failure to follow proper R-454B dissipation system installation
instructions can result in property damage, personal injury, or death. If
any fault codes are listed, please troubleshoot to prevent system
malfunction.
WARNING
!
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing or servicing unit, always turn off all power to the unit.
There may be more than one disconnect switch. Turn off accessory
heater power if applicable. Lock out and tag switch with a suitable
warning label.
have
a factory-installed TXV and are

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the FMU5X and is the answer not in the manual?

Questions and answers

Summary of Contents for Carrier FMU5X

  • Page 1: Table Of Contents

    INSTALLATION ........3 as the fan coil for split -system heat pumps or air conditioners. FMU5X Check Equipment.
  • Page 2: Explosion Hazard

    FMU5X, FMU5Z: Installation Instructions b. The area of any openings above 11-3/16" (300mm) from the WARNING floor shall not be considered in determining compliance with Anvmin. EXPLOSION HAZARD c. At least 50% of the opening area of Anvmin shall be below 7-7/8"...
  • Page 3: Installation

    FMU5X, FMU5Z: Installation Instructions Table 1 – (Continued)Minimum Opening Area for Connected Table 4 – Minimum Circulation Airflow Mmax Anvmin Amin/Tamin Amin/Tamin 17-3 11-5 0.08 lb-oz lb-oz 17-3 12-0 0.07 202.3 11-0 11.0 506.6 17-3 12-10 0.06 4-13 222.7 11-7 11.4...
  • Page 4 FMU5X, FMU5Z: Installation Instructions For Conversion to Horizontal Return: After Mounting Unit, Install Refrigeration Tubing as Follows: 1. Remove the back panel from the casing assembly. 1. Route tubing to connection points. 2. Using the dimples on the back of the casing as a guide, pre-cut the 2.
  • Page 5: Supply-Air Connections

    FMU5X, FMU5Z: Installation Instructions NOTE: Accessory UV-C lights are not approved for use with this fan CAUTION coil. ENVIRONMENTAL HAZARD Failure to follow this caution may result in environmental damage. Do not vent refrigerant to atmosphere. Recover during system repair or final unit disposal.
  • Page 6 FMU5X, FMU5Z: Installation Instructions All units are shipped from factory wired for 240VAC transformer FAN COIL HEAT PUMP THERMOSTAT operation. For 208VAC operation, move primary lead from 240VAC (CONTROL) (CONTROL) terminal to 208VAC terminal. Fig. 4, and Fig. 5 for field low-voltage wiring See Fig.
  • Page 7: Txv

    FMU5X, FMU5Z: Installation Instructions NOTE: The TXVs are preset at the factory and do not need adjustment CAUTION: WIRING DIAGRAM for reliable operation. NOT SUITABLE FOR USE ON SYSTEMS EXCEEDING 150V TO GROUND. ATTENTION: WARNING SEE NAME PLATE FOR VOLT&HERTZ NE CONVIENT PAS AUXINSTALLATIONS DE PLUS DE 150V ALA TERRE.
  • Page 8: Leak Dissipation System Self-Test

    FMU5X, FMU5Z: Installation Instructions The A2L Detection Sensor is attached to a wiring harness that connects the sensor to the control board. Refer to Fig. 4 Fig. 5 for low voltage field connections between the control board and the thermostat. All control wires are labeled with the wire function and landing point.
  • Page 9: Continuous Fan

    FMU5X, FMU5Z: Installation Instructions Continuous Fan CARE AND MAINTENANCE Thermostat closes R to G. G energizes and completes circuit to indoor For continuing high performance and to minimize possible equipment blower motor. When G is de-energized, there is a 90 sec blower failure, it is essential that periodic maintenance be performed on this off-delay.
  • Page 10: Shock Hazard

    FMU5X, FMU5Z: Installation Instructions DUCTWORK Connections for control wiring are made with wire nuts. Control wiring knockouts (5/8"and 7/8") are also provided on the right and left side of Field ductwork must comply with the National Fire Protection the unit for side connection.
  • Page 11 FMU5X, FMU5Z: Installation Instructions Table 8 – PSC -Airflow Performance (Standard CFM) CFM Wet Coil without Filter or Electric Heat, Cased, Bottom Return MODEL (SIZE, TON) MOTOR SPEED External Static Pressure-Inches W.C.[kPa] 0[0] 0.05[.0125] 0.1[.025] 0.15[.0375] 0.2[.050] 0.25[.0625] 0.3[.075] 0.35[.0875]...
  • Page 12 Table 10 – Required CFM Range for Cooling or Heat Pump Operation SIZE Min. Max. 1125 1350 © 2024 Carrier. All rights reserved. Edition Date: 07/24 Catalog No: IM-FMU5-01 Replaces: New Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.