Champ VMVL and PVML high lumen LED luminaires
Installation & maintenance information
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
APPLICATION
Champ® VMVL/PVML Series 13, 17, 21, 25,17-M2, 21-M2, 25-M2
Champ
VMVL luminaires are suitable for use in certain hazardous
®
(classified) areas as defined by the National Electrical Code (NEC
Champ
®
PMVL luminaires are not suitable for use in these NEC
classified areas.
VMVL 13 through 25:
Input voltage:
IEC/ATEX standards (UNV1 Only)
• IEC 60079-0, 7th Edition / EN IEC 60079-0:2018
UNV1
• IEC 60079-7:2010, 5.1 Edition / EN 60079-7:2015
• IEC 60079-31:2008, 2nd Edition / EN 60079-31:2014
• 100-277 VAC, 50/60 HZ NEC
8
• IEC 60529:2001 / EN 60529:2001
• 100-240 VAC, 50/60 HZ EN/IEC
• IEC 60598-1:2008 / EN 60598-1:2008
• 127-250 VDC
• IEC 60598-2:2008 / EN 60598-2:2008
• IEC 60079-18:2017, 4.1 Edition / EN 60079-18:2015 +
UNV34
A1:2017
• 347-480 VAC, 50/60 HZ NEC/CEC
Luminaire markings (UNV1 Only)
• IECEx UL 14.0031X
NEC/CEC
8
• DEMKO 14 ATEX 1324722X
7
• Class I, Division 2, Groups A, B, C, D
CUSTOMER TERMINATION
• DEMKO 14 ATEX 2274231X
• Class II, Groups E, F, G
• Class III
100-277 VAC/127-250 VDC (UNV1 base luminaire
• Class I, Zone 2 AEx ec mb IIC (UNV1 Only)
only)
• Ex ec mb IIC Gc (UNV1 Only)
II 3 G EX ec mb IIC T* Gc -40°C to +40°C
• Zone 21 AEx/Ex tb IIIC Db (UNV1 Only)
BROWN
• Simultaneous Presence
II 3 G EX ec mb IIC T* Gc -40°C to +55°C
L
• Wet Locations, Type 4X
II 3 G EX ec mb IIC T* Gc -40°C to +65°C
CUSTOMER TERMINATION
II 2 D Ex tb IIIC T**°C Db -40°C to +40°C
INPUT
UL standards
II 2 D Ex tb IIIC T**°C Db -40°C to +55°C
• UL 844 Hazardous (Classified)
BLUE
II 2 D Ex tb IIIC T**°C Db -40°C to +65°C
• UL1598 Luminaires, UL1598A Marine
DRIVER
N
CSA standard
BROWN
• CSA C22.2 No. 137
GREEN/YELLOW
L
G
For EMC compliance:
INPUT
If the dimming interface of the LED driver are connected to an external dimmer which is not provided with the luminaire, a ferrite core must be
BLUE
used on the input and dimming lines. Approved ferrite cores are Fair-Rite P/N 0431167281.
N
WARNING
DRIVER
GREEN/YELLOW
COMPARTMENT
To avoid the risk of fire, explosion or electric shock, this product
GROUND
G
should be installed, inspected and maintained by a qualified
electrician only, in accordance with all applicable electrical codes.
INPUT
C
WARNING
DRIVER
To avoid electric shock:
DRIVER
WIRING DIAGRAM 13,
COMPARTMENT
17, 21 and 25 UNV1
GROUND
Be certain electrical power is OFF before and during installation and
maintenance.
INPUT
Luminaire must be supplied by a wiring system with an equipment
grounding conductor.
To avoid burning hands:
WIRING DIAGRAM 13,
Make sure lens and housing are cool when performing
17, 21 and 25 UNV1
maintenance.
INSTALLATION
MOUNTING:
1.
Mount the cover module in its support position.
• Ceiling and wall mount: mark and drill desired location on mounting
surface. Secure with 1/4" (6mm) bolts or lag screws (not
provided).
• Pendant, cone, stanchion mount: securely thread onto the
appropriate NPT size conduit. Tighten set screw located in the
conduit hub. See Figure 1.
• Eaton's Crouse-Hinds HTL thread lubricant must be added to the
conduit threads to prevent water from entering the luminaire.
Open
FIGURE 1
hinge
Set screw
Ground wires
IF 1912 • 08/21
Copyright © 2021, Eaton's Crouse-Hinds Division
Refer to the luminaire nameplate for specific classification information,
maximum ambient temperature suitability and corresponding operating
temperature (T-code).
Luminaire construction is designed for use indoors and outdoors in
®
).
marine and wet locations, where moisture, dirt, corrosion, vibration
and rough usage may be present.
PVML 13 through 25:
Input voltage:
UNV1
• 100-277 VAC, 50/60 HZ
7
6
• 127-250 VDC
UNV34
• 347-480 VAC, 50/60 HZ
Certifications & compliances
• Wet location, Type 4X
6
• IP66
YELLOW
VAUX
VIOLET
UL standards
DIM+
• UL1598 Luminaires, UL1598A
GREY
DRIVER
DIM-
• UL8750
BLACK
• UL50, UL50E
RED
CSA standard
YELLOW
OUTPUT
VAUX
• CSA C22.2 No. 250.0-08
VIOLET
DIM+
SPLICE
IEC standard (UNV1 Only)
GREY
CONNECTORS (x4)
DIM-
• IEC 60598
SPLICE
BLACK
CONNECTOR
RED
OUTPUT
YELLOW
VAUX
SPLICE
VIOLET
DIM+
CONNECTORS (x4)
SPLICE
GREY
DIM-
DRIVER
WARNING
CONNECTOR
BLACK
To avoid explosion:
RED
Make sure the supply voltage is the same as the luminaire voltage.
YELLOW
OUTPUT
VAUX
LED PCB
Do not install where the marked operating temperatures exceed
VIOLET
CONNECTIONS
DIM+
the ignition temperature of the hazardous atmosphere.
GREY
DIM-
Do not operate in ambient temperatures above those indicated on
BLACK
the luminaire nameplate.
RED
Use proper supply wiring as specified on the luminaire nameplate.
OUTPUT
All gasket seals must be clean.
LED PCB
CONNECTIONS
Before opening, electrical power to the luminaire must be turned
off. Keep tightly closed when in operation.
To reduce the risk of ignition due to electrostatic discharge, avoid
contact with the luminaire while explosive atmosphere is present.
Clean only with damp cloth.
WIRING:
1.
Pull field wiring into cover module.
2.
Close all unused conduit entries with conduit plugs provided. To
prevent galling and to ensure watertightness, lubricate conduit
plugs with Eaton's Crouse-Hinds HTL lubricant before installing,
and secure wrench-tight with at least five (5) full threads engaged
(42-52 ft.-lb. for 3/4" plugs, and 58-68 ft.-lb. for 1" plugs).
3.
Hang LED luminaire on the cover module hinge hook.
4.
Connect supply wires to luminaire wire leads or terminal block per
the attached wiring diagrams using methods that comply with all
applicable codes. See Figure 2. Tighten all electrical connections.
5.
Close driver housing onto cover module, making sure that all wires
are safely inside driver housing. Tighten captive closing screw to
30 in.-lbs. (3.4 N-m). Ensure two (2) bosses on driver housing are
in contact with cover module.
6.
Turn power on.
D
IF 1912
5
C
5
Marine
B
A
N
G
Page 1
IF 1912 • 08/21
CUSTOMER TERMINATION
DRIVER
BROWN
L
INPUT
BLUE
N
SPLICE
CONNECTOR
GREEN/YELLOW
G
DRIVER
DRIVER
4
3
COMPARTMENT
GROUND
INPUT
OUTPUT
CUSTOMER TERMINATION
WIRING DIAGRAM
WIRING DIAGRAM 13,
4
3
13, 17, 17-M2, 21, 21-M2, 25, 25-M2 UNV1
17, 21 and 25 UNV1
BLACK- ORANGE
L
CUSTOMER TERMINATION
BLACK-WHITE
DRIVER
N
BLACK- ORANGE
GROUND CASE
L
G
BY FASTENING
INPUT
BLACK-WHITE
DRIVER
N
DRIVER
COMPARMENT
GROUND
WIRING DIAGRAM
GROUND CASE
G
BY FASTENING
13 UNV34
INPUT
DRIVER
COMPARMENT
GROUND
WIRING DIAGRAM
WIRING DIAGRAM
13 UNV34
13 UNV34
CUSTOMER TERMINATION
BLACK-ORANGE
L
CUSTOMER TERMINATION
BLACK-WHITE
DRIVER
N
GROUND CASE
BY FASTENING
G
BLACK-ORANGE
L
INPUT
OUTPUT
DRIVER
BLACK-WHITE
DRIVER
COMPARMENT
GROUND
GROUND CASE
BY FASTENING
INPUT
OUTPUT
DRIVER
GROUND CASE
DRIVER
BY FASTENING
COMPARMENT
GROUND
8
7
INPUT
OUTPUT
GROUND CASE
DRIVER
BY FASTENING
WIRING DIAGRAM
WIRING DIAGRAM
17, 21, 25 UNV34
17, 17-M2, 21, 21-M2, 25, 25-M2 UNV34
FIGURE 2
INPUT
OUTPUT
Copyright © 2021, Eaton's Crouse-Hinds Division
WIRING DIAGRAM
17, 21, 25 UNV34
YELLOW
VAUX
VIOLET
DIM+
GREY
DIM-
BLACK
RED
OUTPUT
SPLICE
CONNECTORS (x4)
YELLOW
VAUX
VIOLET
DIM+
GREY
DIM-
2
BLACK
RED
LED PCB
CONNECTIONS
2
VIOLET
DIM +
GREY
DIM -
SPLICE CONNECTORS (x2)
BLACK
VIOLET
RED
DIM +
GREY
DIM -
OUTPUT
LED PCB
SPLICE CONNECTORS (x2)
CONNECTIONS
BLACK
RED
OUTPUT
LED PCB
CONNECTIONS
VIOLET
DIM +
GREY
DIM -
SPLICE CONNECTIONS (x4)
13L-25L WIRING DIAGRA
BLACK
RED
VIOLET
DIM +
GREY
DIM -
SPLICE CONNECTIONS (x4)
VIOLET
BLACK
GREY
RED
BLACK
6
VIOLET
RED
GREY
LED PCB
CONNECTIONS
BLACK
RED
LED PCB
CONNECTIONS
1
5
Page 2
Need help?
Do you have a question about the Champ VMVL Series and is the answer not in the manual?