Note the warnings or error messages upon completion of the parameter
identification.
No signal is present at digital input S1IND. If a signal was
already
applied
commissioning, the "S1Ind" message is not displayed.
GB
Confirm the final "rEAdY" message by pressing the
ENT key.
Cancelling the operation with the ESC key or withdrawing
the enable signal S1IND results in an incomplete take-over
of the values.
Confirm the "End" display by pressing the ENT key.
The guided commissioning of the frequency inverter is
terminated via a reset and the initialization of the frequency
inverter. The relay output X10 signals a fault.
After successful initialization of the frequency inverter, the
factory-set parameter Actual Frequency 241 is displayed.
The drive is accelerated to the set Min. frequency 418
(default 3.50 Hz) by:
Signals at digital inputs S1IND and S3IND
Start clockwise by rising signal edge at S2IND or Start
anticlockwise by rising signal edge at S3IND
82
at
the
The parameter identification feature of the frequency inverter
requires the presence of a signal at digital input S1IND for release
of the power unit.
In the case of more demanding requirements regarding the
accuracy of the speed/torque control, you should carry out the
guided commissioning procedure once again under operating
conditions because part of the machine data depends on the
operating temperature.
During this procedure, confirm the rated machine values
already entered.
Quick Start Guide ACT
beginning
of
the
guided
12/20