System Specifications - Toshiba TOSDIC-CIE DS Manual

Hide thumbs Also See for TOSDIC-CIE DS:
Table of Contents

Advertisement

Appendix 1. Ethernet Control LAN Network Construction Guide

System Specifications

The following table shows the transmission line specifications for the 100M Ethernet Control LAN.
The 100M Ethernet Control LAN basically complies with the IEEE802.3u specification.
Table A1.2 100M Ethernet Control LAN Transmission Line Specifications
Item
Complied Standards
Transmission Configuration Star Type
Transmission Speed
Medium Access Method
Transmission Signal
No. of Connected Stations
Transmission Line Length
Transmission Cable
Connector Shape
Transmission Line
Redundancy
26
IEEE 802.3
- 100BASE-TX
- 100BASE-FX
100Mbps
CSMA/CD
Base Band
Maximum 64 stations/system
- PCS-DS :32 stations
- OIS-DS
:22 stations
- SVR-DS :2 stations
- Other EWS, etc. :8 stations
Total Expansion Distance :Maximum 8.0km
100BASE-TX :Maximum 30m
Max. of 3m between a TX hub and FX-TX conversion module
100BASE-FX :2km
Max. of 150m between a TX shub and TX hub
100BASE-TX :Twisted Pair Cable (Category 5)
100BASE-FX :Optical Fiber (Graded Index Type)
GI 62.5/125 Long Wave Length
100BASE-TX :RJ-45 Modular Connector
100BASE-FX :SC-type Optical Connector
Standard
Specification

Advertisement

Table of Contents
loading

Table of Contents