Water Cooling Set Temp - LG THERMA V HM141MR Installation Manual

Air-to-water heat pump
Table of Contents

Advertisement

INSTALLER SETTING
216

Water cooling set temp.

Determine cooling setting temperature range when water temperature is selected as setting
temperature.
• In the installer setting list, select water cooling set temp category, and press [OK] button to
move to the detail screen.
Value
Min.
Max.
NOTE
Water condensation on the floor
• While cooling operation, it is very important to keep leaving water temperature higher than
16 °C. Otherwise, dew condensation can be occurred on the floor.
• If floor is in humid environment, do not set leaving water temperature below 18 °C.
Water condensation on the radiator
• While cooling operation, cold water may not flow to the radiator. If cold water enters to
the radiator, dew generation on the surface of the radiator can be occurred.
Default
Range
5~20 °C
18 °C
16~20 °C
10~20 °C
20 °C
20 °C
24 °C
22~27 °C
OK
Cooling temp. setting
Outlet
Inlet
FCU use
FCU not used
FCU use
FCU not used
All

Advertisement

Table of Contents
loading

Table of Contents